This article explains converting kvar to kW precisely using kVA and power factor measurements securely.
Engineers, technicians, and energy managers will apply formulas, examples, and regulatory references for system design.
kVAr to kW Conversion Calculator with kVA and Power Factor
Overview of reactive and real power relationships
Electrical power in alternating current (AC) systems comprises real power (kW), reactive power (kvar), and apparent power (kVA). The three quantities relate geometrically via the power triangle, where kVA is the hypotenuse, kW is the adjacent side, and kvar is the opposite side.
Power factor (PF) is the cosine of the phase angle between voltage and current and determines the distribution of kW and kvar within kVA. A correct understanding of these relationships is essential for accurate conversion and equipment sizing.

Core formulas and variable definitions
Fundamental conversion relations required by a free kvar to kW calculator with known kVA and power factor:
- kW = kVA × PF
- kvar = kVA × sqrt(1 − PF × PF)
- kvar = sqrt(kVA × kVA − kW × kW)
- Given kW and PF, kVA = kW / PF
Meaning of variables and typical ranges
- kW — kilowatts: real (active) power delivered to load. Typical values range from a few watts in electronics to megawatts in substations.
- kvar — kilovolt-amperes reactive: reactive power needed to establish magnetic fields in inductive loads or provide reactive compensation. Usually positive for inductive loads, negative for capacitive.
- kVA — kilovolt-amperes: apparent power, vector sum of kW and kvar. Equipment ratings (transformers, UPS, generators) are given in kVA.
- PF — power factor: dimensionless, between 0 and 1 in magnitude for non-harmonic pure sinusoidal systems. Typical industrial PF values: 0.65–0.95.
Algebraic derivations and calculator logic
To implement a precise conversion in seconds, follow the algebraic logic below. All formulas are provided in plain HTML notation for direct implementation in spreadsheets, scripts, or calculators.
Direct kW from kVA and PF
Example typical values: kVA = 100, PF = 0.8 → kW = 100 × 0.8 = 80 kW.
Reactive kvar from kVA and PF
Explanation: sqrt(1 − PF × PF) equals sin(theta) when PF = cos(theta). Example: kVA = 100, PF = 0.8 → kvar = 100 × sqrt(1 − 0.64) = 100 × 0.6 = 60 kvar.
Alternative reactive calculation from kW and PF
When kW and PF are given, compute kvar by first computing kVA or directly with Pythagoras:
Extensive conversion table for common kVA and PF combinations
The following table provides quick lookup values of kW and kvar across typical kVA ratings and power factors frequently encountered in industrial, commercial, and utility contexts.
| kVA | PF | kW (kVA × PF) | kvar (kVA × sqrt(1 − PF²)) |
|---|---|---|---|
| 10 | 0.60 | 6.00 | 8.00 |
| 10 | 0.70 | 7.00 | 7.14 |
| 10 | 0.80 | 8.00 | 6.00 |
| 10 | 0.90 | 9.00 | 4.36 |
| 10 | 1.00 | 10.00 | 0.00 |
| 25 | 0.60 | 15.00 | 20.00 |
| 25 | 0.70 | 17.50 | 17.85 |
| 25 | 0.80 | 20.00 | 15.00 |
| 25 | 0.90 | 22.50 | 10.90 |
| 25 | 1.00 | 25.00 | 0.00 |
| 50 | 0.60 | 30.00 | 40.00 |
| 50 | 0.70 | 35.00 | 35.71 |
| 50 | 0.80 | 40.00 | 30.00 |
| 50 | 0.90 | 45.00 | 21.79 |
| 50 | 1.00 | 50.00 | 0.00 |
| 75 | 0.60 | 45.00 | 60.00 |
| 75 | 0.70 | 52.50 | 53.56 |
| 75 | 0.80 | 60.00 | 45.00 |
| 75 | 0.90 | 67.50 | 32.69 |
| 75 | 1.00 | 75.00 | 0.00 |
| 100 | 0.60 | 60.00 | 80.00 |
| 100 | 0.70 | 70.00 | 71.42 |
| 100 | 0.80 | 80.00 | 60.00 |
| 100 | 0.90 | 90.00 | 43.59 |
| 100 | 1.00 | 100.00 | 0.00 |
| 250 | 0.60 | 150.00 | 200.00 |
| 250 | 0.70 | 175.00 | 178.54 |
| 250 | 0.80 | 200.00 | 150.00 |
| 250 | 0.90 | 225.00 | 108.97 |
| 250 | 1.00 | 250.00 | 0.00 |
| 500 | 0.60 | 300.00 | 400.00 |
| 500 | 0.70 | 350.00 | 357.09 |
| 500 | 0.80 | 400.00 | 300.00 |
| 500 | 0.90 | 450.00 | 217.95 |
| 500 | 1.00 | 500.00 | 0.00 |
Capacitor sizing table: kvar required to improve power factor to 0.95
This table shows the reactive compensation (kvar) needed to raise a plant's PF from a common initial value to a target PF of 0.95. The formula used:
| kW | PF_initial | PF_target | kvar required (approx.) |
|---|---|---|---|
| 50 | 0.70 | 0.95 | 34.58 |
| 100 | 0.70 | 0.95 | 69.16 |
| 250 | 0.70 | 0.95 | 172.89 |
| 500 | 0.70 | 0.95 | 345.79 |
| 50 | 0.85 | 0.95 | 14.56 |
| 100 | 0.85 | 0.95 | 29.11 |
| 250 | 0.85 | 0.95 | 72.78 |
| 500 | 0.85 | 0.95 | 145.56 |
Step-by-step calculator algorithm (for implementation)
- Accept user inputs: one of {kVA and PF} or {kW and PF} or {kVA and kvar} depending on available data.
- Normalize PF: ensure PF is between 0 and 1 (absolute value for sign awareness, determine inductive or capacitive behaviour with sign convention).
- Compute kW when kVA and PF provided: kW = kVA × PF.
- Compute kvar when kVA and PF provided: kvar = kVA × sqrt(1 − PF × PF).
- If kW and PF provided, compute kVA = kW / PF then kvar = sqrt(kVA² − kW²) or use kvar = kW × sqrt(1 / (PF × PF) − 1).
- Format results, include units, and optionally compute percent of reactive to apparent power (kvar/kVA × 100%) and PF improvement suggestions.
Excel / Spreadsheet formulas for quick implementation
- Given kVA in cell A2 and PF in B2: kW formula => =A2*B2
- Given kVA in A2 and PF in B2: kvar formula => =A2*SQRT(1-B2*B2)
- Given kW in C2 and PF in D2: kVA formula => =C2/D2
- Given kW in C2 and PF in D2: kvar formula => =C2*SQRT(1/(D2*D2)-1)
Practical examples — solved step-by-step
Example 1 — Convert kvar to kW when kVA and PF are known (industrial transformer)
Scenario: A distribution transformer is rated at 250 kVA supplying predominantly motor loads. Measured power factor is 0.78 (lagging). Compute kW and kvar.
Step 3 — Verify using Pythagoras: sqrt(kVA² − kW²) = sqrt(250² − 195²) = sqrt(62500 − 38025) = sqrt(24475) = 156.45 kvar (match).
Result: 195.00 kW and 156.45 kvar. Use these values for transformer loading checks and reactive compensation calculations.
Example 2 — Compute capacitor sizing to raise PF from 0.72 to 0.95 for 300 kW load
Scenario: A manufacturing line draws 300 kW at PF = 0.72 (lagging). The utility requires a minimum PF of 0.95. Compute required kvar of capacitors to correct PF to 0.95.
Step 1 — Use the formula for Q (reactive) per kW: Q = kW × sqrt(1 − PF²) / PF
Compute initial tangent factor: sqrt(1 − 0.72²) / 0.72
Step 2 — Compute Q at target PF 0.95
Result: Install approximately 190.4 kvar of capacitors. Implementation notes: stage banks to avoid overcompensation at light loads, include switching and inrush control, and coordinate with protective relays.
Measurement techniques and instrumentation
- Clamp meters with true-RMS and PF measurement can give instantaneous kW and PF for single-phase or balanced polyphase loads.
- Three-phase power analyzers measure line-to-line and line currents to compute total kW, kvar, and kVA accurately; important for unbalanced systems.
- Use instrument transformers (CTs/VTs) sized appropriately for high-voltage systems; ensure burden and phase accuracy per manufacturer specs.
- Apply harmonic analysis where non-linear loads exist. Harmonics distort PF readings and require different treatment (harmonic compensation or detuned filters).
Harmonics and power factor interpretation
Distinguish between displacement PF (fundamental frequency phase shift) and total PF (includes harmonic distortion). IEEE and IEC guidance separate distortion PF and displacement PF; a converter that ignores harmonics can misestimate required capacitors.
Safety, operational, and regulatory considerations
- Ensure capacitor installations comply with local codes and safety standards; include discharge resistors, fusing, and switching gear coordination.
- Verify transformer and conductor ratings before adding capacitors to avoid resonance and overvoltage conditions.
- Coordinate PF correction strategy with utility tariff rules: many utilities charge penalties for low PF and may offer incentives for correction.
- Measure and document pre- and post-compensation performance to verify compliance and economic return on investment (ROI).
References and authoritative resources
For regulatory and technical guidance, consult the following standards and publications. These resources provide definitions, measurement methods, and recommended practices for power factor and reactive compensation:
- IEEE Std 141 — The IEEE Green Book (Power Distribution for Industrial Plants). https://ieeexplore.ieee.org/ (search IEEE 141)
- IEC 60038 — IEC Standard Voltages. https://www.iec.ch/
- IEEE Std 1459 — Definitions for the Measurement of Electric Power Quantities under Sinusoidal, Nonsinusoidal, Balanced or Unbalanced Conditions. https://standards.ieee.org/
- NIST (National Institute of Standards and Technology) publications on electrical measurements. https://www.nist.gov/
- U.S. Department of Energy (DOE) resources on power factor correction and industrial efficiency. https://www.energy.gov/
Best practices for using a free kvar to kW calculator
- Always verify input units and phase basis (single-phase vs three-phase). Convert single-phase kVA to three-phase equivalents when necessary: for three-phase systems, kVA_total = √3 × V_line × I_line / 1000 (if measuring line current and line voltage).
- Understand sign conventions: reactive power can be positive (inductive) or negative (capacitive). For PF correction using capacitors, expect kvar reduction on inductive systems.
- When planning compensation, stage capacitor banks to match load variability and avoid over-correction during low-load periods.
- Account for harmonic distortion by using detuned filters or harmonic-capable capacitors where converters and VFDs are present.
Useful implementation tips
- Provide both instantaneous results and a time-averaged value if input signals vary rapidly; average PF over relevant billing periods to compute penalties and ROI.
- Include sanity checks in the calculator: PF must be ≤ 1.0, kVA must be ≥ kW, and computed kvar should be real-valued (no negative under square root).
- Offer the option to compute reverse conversions: given kW and kvar return kVA and PF to support troubleshooting.
Summary of conversion formulas for rapid reference
Compact formulas that an engineer or technician can keep as quick references:
- kW = kVA × PF
- kvar = kVA × sqrt(1 − PF²)
- kVA = kW / PF
- kvar = sqrt(kVA² − kW²) = kW × sqrt(1 / PF² − 1)
Additional resources and further reading
- IEEE Xplore Digital Library for standards and technical papers on power quality and PF correction. https://ieeexplore.ieee.org/
- IEC webstore and technical committees for international electrical standards. https://www.iec.ch/
- Energy efficiency guides and calculators from national energy agencies: U.S. DOE, UK BEIS, and EU energy resources.
Using the formulas and tables in this article, engineers can convert between kvar, kW, and kVA in seconds, size capacitors for PF correction accurately, and verify equipment ratings against real and reactive loads. Always cross-check calculations with precise measurements and applicable standards before implementing changes to distribution systems.