Calculator Three Phase Voltage Drop Calculation: Epic, Best

This article provides advanced three-phase voltage drop calculation methods with precision, clarity, and practical guidance.

Engineers require accurate calculators, normative compliance, and interpretative examples for reliable electrical design decisions worldwide.

Three-Phase Voltage Drop Calculator — Technical

Upload a datasheet or diagram photo to suggest conductor and installation values.

Enter all parameters to obtain voltage drop and percentage.
Formulas and methodology
Current calculation (if using power): I = P(kW)·1000 / (√3 · V_LL · cosφ). Units: A.
Temperature correction for R: R_T = R_20 · [1 + α · (T - 20)], α_Cu = 0.00393 °C⁻¹, α_Al = 0.00403 °C⁻¹. R_20 in Ω/km; convert to Ω/m by dividing by 1000.
Three-phase voltage drop (magnitude): ΔV = √3 · I · (R_m · cosφ + X_m · sinφ) · L
Percentage voltage drop: %ΔV = (ΔV / V_LL) · 100
Conductor I²R loss (approx.): Loss = I² · R_total where R_total = R_m · L. Units: W.
Conductor (Cu) mm²R at 20°C (Ω/km)Typical X (Ω/km)
1.512.100.08
2.57.410.08
44.610.08
63.080.08
101.830.08
161.150.08
250.7270.08
350.5240.08
500.3870.08
700.2680.08
950.1930.08
FAQ
Q: Which length should be used: one-way or round-trip?
A: Use one-way conductor length L in the formula; the formula already accounts for the three-phase geometry. Do not double the length.
Q: How is reactance chosen?
A: Reactance depends on cable type and formation (trefoil, single-core spacing). Use manufacturer data when available; otherwise use the 'Typical' preset (≈0.08 Ω/km) as an engineering estimate.
Q: What is acceptable voltage drop?
A: Common criteria: ≤3% for final circuits, ≤5% for feeders and mains (check project/standard requirements).

Fundamentals of Three-Phase Voltage Drop

Voltage drop in three-phase systems is the result of the impedance of conductors carrying current. For a balanced three-phase load the line-to-line voltage drop magnitude is dominated by the product of current, conductor impedance per unit length, electrical length, and the load phase angle. Key influences on voltage drop:
  • Conductor material (copper, aluminium) and cross-sectional area (mm²)
  • Conductor AC resistance and reactance per unit length (R, X in ohm/km)
  • Load current magnitude I (A) and power factor φ (cosφ)
  • Physical length of the run L (km) and grouping/corridor installation effects
  • Operating temperature and temperature coefficient of resistance

Balanced three-phase formula (line-to-line)

ΔV = √3 × I × (R cosφ + X sinφ) × L
Variables:
  • ΔV: Line-to-line voltage drop (V)
  • I: Line current per phase (A)
  • R: Conductor resistance per unit length (ohm/km) at reference temperature
  • X: Conductor reactance per unit length (ohm/km)
  • φ: Load phase angle (power factor angle), where cosφ is power factor
  • L: One-way conductor length (km)
Note: For phase (line-to-neutral) voltage drop use:
ΔV_phase = I × (R cosφ + X sinφ) × L
and for percentage drop:
%ΔV = (ΔV / V_line) × 100
where V_line is the nominal line-to-line system voltage (for example 400 V in many LV networks).

Temperature correction of resistance

Conductor resistance varies with temperature. Use:
R_T = R_20 × [1 + α × (T - 20)]
Where:
  • R_T: resistance at operating temperature T (°C)
  • R_20: resistance at 20 °C (ohm/km)
  • α: temperature coefficient (≈0.00393 /°C for copper, ≈0.00403 /°C for aluminium)
  • T: conductor operating temperature (°C)
Example typical values: If R_20 = 0.3448 ohm/km for Cu 50 mm² and conductor T = 75 °C, α = 0.00393:
R_75 = 0.3448 × [1 + 0.00393 × (75 - 20)] = 0.3448 × [1 + 0.216] ≈ 0.419
(ohm/km)

Typical conductor parameters and reference tables

Below are extensive typical reference tables used in practical voltage drop calculators. Values are representative at 20 °C for resistance and typical reactance for 50 Hz installations; verify with local code or manufacturer data for high accuracy.
Cu conductor (mm²) R @20°C (ohm/km) Typical X @50Hz (ohm/km) R @75°C (ohm/km) (approx)
1.511.4940.08013.97
2.56.8960.0808.38
44.3100.0805.24
62.8730.0803.49
101.7240.0782.09
161.07760.0781.31
250.68960.0760.84
350.49260.0750.60
500.34480.0730.42
700.24630.0710.30
950.18150.0700.22
1200.14370.0690.18
1500.11490.0680.14
1850.09320.0670.11
2400.07180.0660.087
Al conductor (mm²) R @20°C (ohm/km) Typical X @50Hz (ohm/km) R @75°C (ohm/km) (approx)
161.76650.0802.31
251.13060.0781.48
350.80900.0771.06
500.56530.0750.74
700.40380.0730.53
950.29750.0710.39
1200.23550.0700.30
1500.18840.0690.24
1850.15270.0680.20
2400.11780.0670.15
Notes on tables:
  • R values are computed from resistivity at 20 °C: copper ≈ 0.017241 ohm·mm²/m, aluminium ≈ 0.028264 ohm·mm²/m.
  • X values are typical for common LV installations and depend on conductor arrangement and spacing; bundling and conduits increase X.
  • Use manufacturer or standards data (IEC 60287) for final design.

Calculator design considerations and UX features

A high-quality three-phase voltage drop calculator must support:
  1. Material selection: copper/aluminium with selectable temperature coefficients.
  2. Conductor size selection with R and X tables and ability to import manufacturer data.
  3. Length units (m, km), current inputs either as I (A) or as power P (kW) with selectable power factor.
  4. System voltage selection (line-to-line), single-phase/three-phase mode, and harmonic load influence.
  5. Temperature correction and grouping/derating factors for bundled cables.
  6. Outputs: absolute voltage drop (V), percentage drop, and recommended upsizing suggestions to meet code limits.
Additional UX elements:
  • Show intermediate steps and formulas for traceability (benefits engineers and auditors).
  • Allow export of calculation report including normative references and assumptions.
  • Include warnings when results exceed common limits or when conductor thermal ratings may be exceeded.

Regulatory and normative limits

Common recommended maximum voltage drops:
Regulatory source Typical recommended limit Scope
IEC/BS 7671 (guidance)Typically 3% branch, 5% totalLow-voltage installations; guidance may vary by country
NEC (NFPA 70) recommendation3% for branch circuits, 5% for feeder+branchRecommended practice in the USA (not mandatory)
IEEE/other engineering practice1%–5% depending on sensitivity of equipmentTransformer and motor sensitive applications often tighter
Always verify local code (national/utility) requirements. Critical power systems, protection relays, and sensitive electronics often require tighter limits (1–2%).

Worked examples with complete development

Below are two full examples demonstrating step-by-step calculations suitable for inclusion in a calculator result page.

Example 1 — Motor feeder, 50 kW three-phase motor at 400 V (Cu conductor)

Scenario:
  • Load: 50 kW three-phase motor
  • System voltage: 400 V (line-to-line)
  • Power factor: cosφ = 0.85 (lagging)
  • Feeder length: 100 m (one-way)
  • Conductor: copper, 50 mm²
  • Ambient conditions: use R_20 values, assume moderate conductor temperature (no further correction in base case)
Step 1 — Calculate line current from power:
I = P / (√3 × V_line × cosφ)
Compute:
  • P = 50,000 W
  • √3 ≈ 1.732
  • V_line = 400 V
  • cosφ = 0.85
I = 50000 / (1.732 × 400 × 0.85) = 50000 / 588.88 ≈ 84.9 A
Step 2 — Conductor parameters:
  • R @20°C for Cu 50 mm² = 0.3448 ohm/km (from table)
  • X typical = 0.073 ohm/km
  • L = 100 m = 0.1 km
  • sinφ = √(1 − cos²φ) = √(1 − 0.7225) = √0.2775 ≈ 0.5268
Step 3 — Compute resistance-reactance weighted term:

(R cosφ + X sinφ) = 0.3448 × 0.85 + 0.073 × 0.5268 = 0.2931 + 0.0385 ≈ 0.3316 (ohm/km)

Step 4 — Apply three-phase formula:
ΔV = √3 × I × (R cosφ + X sinφ) × L
Compute:

ΔV = 1.732 × 84.9 × 0.3316 × 0.1 ≈ 1.732 × 84.9 × 0.03316 ≈ 1.732 × 2.815 ≈ 4.876 V

Calculator Three Phase Voltage Drop Calculation Epic Best for Accurate Results
Calculator Three Phase Voltage Drop Calculation Epic Best for Accurate Results
Step 5 — Percentage drop:
%ΔV = (4.876 / 400) × 100 ≈ 1.22%
Result summary:
  • Line current ≈ 84.9 A
  • Voltage drop ≈ 4.9 V (1.22%) — well within typical 3% branch limit
If conductor operating temperature is high (e.g., 75 °C), apply temperature correction to R then recompute. Temperature correction increases R and proportionally increases ΔV.

Example 2 — Long distribution feeder, aluminium conductors

Scenario:
  • Feeder: 300 A balanced three-phase load at 400 V
  • Power factor: cosφ = 0.95
  • Length: 200 m (0.2 km)
  • Conductor: aluminium, 150 mm²
Step 1 — Given line current:
I = 300 A (stated)
Step 2 — Conductor parameters:
  • R @20°C for Al 150 mm² = 0.1884 ohm/km
  • X typical = 0.069 ohm/km
  • L = 0.2 km
  • sinφ = √(1 − 0.95²) = √(1 − 0.9025) = √0.0975 ≈ 0.31225
Step 3 — Weighted impedance term:

(R cosφ + X sinφ) = 0.1884 × 0.95 + 0.069 × 0.31225 = 0.1790 + 0.0215 = 0.2005 (ohm/km)

Step 4 — Apply three-phase formula:
ΔV = √3 × I × (R cosφ + X sinφ) × L
Compute:

ΔV = 1.732 × 300 × 0.2005 × 0.2 = 1.732 × 300 × 0.04010 ≈ 1.732 × 12.03 ≈ 20.84 V

Step 5 — Percentage:
%ΔV = (20.84 / 400) × 100 ≈ 5.21%
Result summary:
  • Voltage drop ≈ 20.8 V (≈5.21%) — exceeds common 5% total limit
  • Mitigation: increase conductor size (e.g., to Al 185 mm²) or reduce length or use copper conductors
Quick upsizing check (Al 185 mm², R ≈ 0.1527 ohm/km):
(R cosφ + X sinφ) ≈ 0.1527×0.95 + 0.068×0.31225 = 0.1450 + 0.0212 = 0.1662
ΔV_new = 1.732 × 300 × 0.1662 × 0.2 ≈ 17.27 V => 4.32%
This drops below 5% but might still be above a 3% target; select accordingly.

Advanced topics and corrections

Grouping and mutual coupling

When multiple circuits are grouped in a conduit, DC resistance stays same but AC resistance and reactance vary due to proximity and skin effect. Corrective factors:
  • Proximity increase effective X and sometimes R; consult IEC 60287 or manufacturer data.
  • Apply grouping correction factors (k_group) to R and X or use tabulated impedance for installed configuration.

Harmonics

Harmonic currents increase RMS current and can increase losses and heating; use:
  • Equivalent RMS current I_eq = √(I1² + I3² + I5² + ...)
  • Calculate voltage drop using I_eq and consider additional skin/proximity effects increasing R and X at harmonic frequencies.

Transformers and unbalanced loads

For systems with significant unbalance or delta-star transformer configurations, calculate per-phase drops individually using phase currents and corresponding conductor impedances. For unbalanced systems the simple balanced formula can underestimate worst-phase drop.

Implementation checklist for an 'Epic Best' calculator

To market a leading three-phase voltage drop calculator emphasize:
  • Precision: allow user override of R/X inputs and include temperature adjustments.
  • Transparency: show step-by-step math and intermediate values.
  • Normative guidance: display recommended maximums per IEC/NEC and allow selection of target limits.
  • Optimization: provide “what-if” upsizing suggestions and auto-search the minimum conductor size meeting limits.
  • Exportable compliance report: include assumptions, normative references, and traceable inputs/outputs.

Normative references and authoritative resources

Key standards and references (authoritative):
  • IEC 60287 — Electric cables — Calculation of the continuous current rating (ampacity) — impedance and losses reference (purchase required); see IEC (https://www.iec.ch)
  • IEC 60364 series / BS 7671 — Requirements for electrical installations (guidance on voltage drop and wiring rules); see national adoption documentation
  • NFPA 70 (NEC) — Article on voltage drop recommendations (United States) (https://www.nfpa.org)
  • Engineering ToolBox — Resistivity, conductor resistance, and X/R typical values (technical reference) (https://www.engineeringtoolbox.com)
  • Electric Power Research Institute (EPRI) or IEEE papers on power system voltage regulation and conductor modeling — consult IEEE Xplore (https://ieeexplore.ieee.org)
When quoting normative values in professional reports, cite the specific clause and year of the standard applicable in your jurisdiction.

Practical tips and validation

Practical steps to validate calculator outputs:
  1. Cross-check R and X values with manufacturer cable data sheets for the exact construction and installation method.
  2. Perform a sensitivity analysis by varying power factor, length, and temperature to identify worst-case drop.
  3. If possible, measure voltage at the remote load in a commissioning test and compare to calculated values (accounting for instrument accuracy).
  4. Include safety margins: when critical equipment is involved, design for a lower percentage drop than the maximum permitted.

Summary of essential formulas and quick reference

Key formulas to include as visible help in any calculator interface:
  • Line current from three-phase power:
    I = P / (√3 × V_line × cosφ)
  • Three-phase line-to-line voltage drop:
    ΔV = √3 × I × (R cosφ + X sinφ) × L
  • Phase (line-to-neutral) voltage drop:
    ΔV_phase = I × (R cosφ + X sinφ) × L
  • Percentage voltage drop:
    %ΔV = (ΔV / V_line) × 100
  • Temperature correction:
    R_T = R_20 × [1 + α × (T - 20)]

References for further reading

Suggested authoritative reading for advanced design:
  • IEC 60287 series — cable impedance and current rating calculations (official standard).
  • BS 7671 (IET Wiring Regulations) — guidance on voltage drop criteria (UK).
  • NFPA 70 (NEC) Handbook articles on voltage drop recommendations (USA).
  • Engineering Toolbox — practical tables and calculators for conductivity and resistivity: https://www.engineeringtoolbox.com
  • IEEE Xplore — technical papers on cable modelling, harmonics and voltage regulation: https://ieeexplore.ieee.org
Use these resources to validate assumptions and to obtain manufacturer-level impedance tables when precision is necessary. Final note: implement traceability in every calculation by logging inputs, chosen tables, temperature assumptions, and normative limits. This enables auditors and clients to understand and trust the 'epic best' three-phase voltage drop calculator results.