This article presents an instant arc flash clearing time calculator derived from protective device settings.
Methodology computes Time-Current Characteristic intersections, using TCC curves and device trip thresholds precisely analyzed here.
Instant Arc Flash Clearing Time Calculator from Protective Device TCC Settings
Arc flash clearing time fundamentals and scope
Arc flash clearing time is the elapsed period from arc initiation to fault interruption by the protective device. It is the principal parameter controlling incident energy, equipment damage, and worker hazard. Calculating clearing time requires accurate device Time-Current Characteristic (TCC) data, the available fault current at the fault location, and any coordination delays introduced by multiple devices. This article provides a rigorous method to compute instantaneous and inverse-time clearing times from protective device settings, including formulas, variable explanations, tables of typical values, and worked examples. Critical distinctions must be observed:- Bolted-fault current (I_bf) is the prospective short-circuit current ignoring arc impedance.
- Arcing current (I_arc) is the empirical current that actually flows in an arc and is typically lower than I_bf; IEEE 1584 provides methods to estimate it.
- Clearing time (t_clear) is the time at which the protective device removes the fault — for arc flash calculations this is the arc duration used to compute incident energy.
Mathematical representation of Time-Current Characteristics (TCC)
TCCs are commonly modeled either by piecewise manufacturer curves or by parameterized functional forms suitable for analytic computation. Two widely used functional prototypes are:1) Inverse power-law model (suitable approximation for many fuses and breakers):
t = A * (I / Ip)B + C

2) Inverse-relay-style model (common for electrical relays with time multiplier settings):
t = TMS * K / ( (I / Ipickup)P - 1 )
Explanation of variables and typical ranges:- t — clearing time (seconds).
- I — fault current magnitude used for the device curve (A). This can be Iarc or Ibf depending on method.
- Ip — reference current (A). For the inverse power-law it is commonly the device pickup or rated current.
- Ipickup — pickup current setting for the relay or trip element (A).
- A, B, C — empirical coefficients to fit the manufacturer TCC into a simple analytic expression. Typical example values (for illustrative modeling only):
- MCCB thermal-magnetic approximate fit: A ≈ 0.2, B ≈ -1.2, C ≈ 0.01.
- Cartridge fuse (highly inverse) approximate fit: A ≈ 1.5, B ≈ -3.0, C ≈ 0.0.
- TMS — Time Multiplier Setting (dimensionless) for adjustable electromechanical/electronic relays.
- K, P — curve constants depending on curve family (standard inverse, very inverse, extremely inverse). Example nominals for modeling:
- Standard inverse: K ≈ 0.14, P ≈ 0.02 (use only as manufacturer-supplied equivalent).
- Very inverse: K ≈ 13.5, P ≈ 1.0.
- Extremely inverse: K ≈ 80.0, P ≈ 2.0.
Relationship between available current and TCC input
Two commonly used choices for the independent current in TCC evaluation are:- Ibf — Bolted-fault current (prospective short-circuit current). This gives a conservative (shorter) computed clearing time if the device reacts primarily to magnitude rather than arc impedance effects. Many protective devices operate on measured current and thus respond to the arcing current actually flowing in the system.
- Iarc — Arcing current calculated by empirical methods (IEEE 1584-2018) which accounts for arc impedance, enclosure, gap, and voltage. Using Iarc yields least-conservative incident energy estimates for arc energy output but is more accurate for the physical arc survival time.
Step-by-step algorithm to compute arc flash clearing time from protective device TCC
Follow these deterministic steps for a reproducible calculation:- Determine system single-line topology and fault location to compute short-circuit current using network impedances (use IEC 60909 or equivalent method).
- Compute prospective bolted-fault current Ibf at the fault point.
- Estimate arcing current Iarc if using IEEE 1584 methodology or retain Ibf if the protective device responds primarily to raw current magnitude and the standard for arc current estimation is not applied.
- Obtain protective device TCC data (manufacturer curve or numeric table). Identify pickup settings, time multiplier, and instantaneous/short-time elements.
- Model TCC as an analytic function or use tabular interpolation to find the time t such that the device curve predicts operation at I (I = Iarc or Ibf depending on choice).
- For multiple upstream protection devices, compute the device expected to operate first (the lowest t at the target fault current) — this is the clearing device. If selective coordination is required, account for clearance by upstream/ downstream device cooperation and possible time delays.
- Report t_clear = computed clearing time. Use this duration in arc flash incident energy computations and PPE selection per NFPA 70E and IEEE 1584.
Mathematical inversion and root finding
For analytic TCC forms such as t = A*(I/Ip)B + C, inversion algebraically gives:I = Ip * ( (t - C) / A )1/B
However, typical use cases require solving for t given I, which is direct evaluation. For relay-style models where t appears on both sides implicitly (rare), numerical root-finding (Newton-Raphson or bisection) may be used. For tabular manufacturer TCCs the common approach is monotonic interpolation on log-log scale.Extensive tables of common device settings and empirical values
| Device type | Typical reference | Model form | Example coefficients (A, B, C or K, P) | Typical instantaneous threshold |
|---|---|---|---|---|
| MCCB (electronic trip) | Manufacturer TCC | t = A*(I/Ip)B + C | A=0.2, B=-1.2, C=0.01 (illustrative) | 2–8× rated current (adjustable) |
| Molded Case Breaker (thermal magnetic) | IEC/ANSI-type curves | t = A*(I/Ip)B + C | A=0.3, B=-1.0, C=0.02 (illustrative) | 5–10× rated current |
| Fuse (HRC / gG) | Manufacturer time-current tables | t = A*(I/Irated)B | A=1.5, B=-3.0 (illustrative) | n/a (no instantaneous element) |
| Overcurrent relay (electromech/electronic) | ANSI/IEEE C37.112 families | t = TMS*K/( (I/Ipickup)P - 1 ) | K,P vary: standard/very/extreme; K≈0.14–80, P≈0.02–2.0 | Instantaneous element: 6–20× pickup |
| Fuse multiple (I/Irated) | Typical clearing time (s) | Application notes |
|---|---|---|
| 5× | ≈1.0–10.0 | May take seconds; not fast clearing |
| 10× | ≈0.1–1.0 | Common high-multiple region for motor-start protection |
| 20× | ≈0.02–0.1 | Fast clearing for sustained faults |
| 50–100× | ≈0.005–0.02 | Near-instantaneous clearing for high-energy faults |
| Breaker instantaneous multiple | Representative clearing time | Notes |
|---|---|---|
| 3× pickup | 0.2–1.0 s | May be cleared by thermal element first |
| 6–10× pickup | 0.05–0.2 s | Instantaneous elements may be active |
| >10× pickup | 0.01–0.05 s | High-energy faults cleared rapidly by electronic trip |
Practical techniques for implementing an instant arc flash clearing time calculator
Key implementation considerations when coding or writing a calculation tool:- Curve data ingestion: allow manufacturer TCC tables (time vs current) and analytic coefficients.
- Interpolation: implement log-log interpolation to preserve slope characteristics across decades.
- Arcing current vs bolted current: include an option to compute Iarc from Ibf per IEEE 1584 or to use Ibf directly.
- Multiple protection evaluation: compute clearing times for all protective devices that could clear the fault and select the earliest time.
- Instantaneous/short-time elements: treat these as separate curve segments or threshold times with fixed clearance times.
- Validation: compare computed times versus published manufacturer TCC charts for sanity checks.
Example of interpolation algorithm (conceptual)
- Convert time and current arrays to log10 scale: x = log10(current), y = log10(time).
- For given log-current, find interval and perform linear interpolation on y.
- Return t = 10y_interpolated.
Worked example 1 — Low-voltage MCCB with instantaneous trip element
Scenario:- System voltage: 480 V three-phase.
- Available bolted-fault current at fault location: Ibf = 25,000 A (25 kA).
- Protective device: Molded Case Circuit Breaker (MCCB) with electronic trip unit, rated 1600 A.
- Settings: long-time pickup (Ip) = 1.0 × 1600 A = 1600 A, instantaneous trip threshold = 10,000 A (10 kA), instantaneous trip operating time (manufacturer max) = 0.03 s.
- TCC modeling: electronic instantaneous trip is dominant because Ibf > instantaneous threshold.
- Compare Ibf with instantaneous threshold: 25 kA > 10 kA → instantaneous element will operate.
- Because instantaneous element is designed to act non-time-delayed, use manufacturer stated instantaneous operating time. For this device assume tinst = 0.03 s (typical electronic trip response).
- Therefore, computed clearing time t_clear = tinst = 0.03 s.
- If instead the instantaneous threshold were higher than Ibf, we would evaluate the inverse-time long-time or short-time curve at I = 25 kA to compute t_clear.
- Note that if multiple upstream devices exist, an upstream device may have a lower clearing time at this current. The calculator must compare times across devices and pick earliest.
Clearing time used for arc flash energy computation: t_clear = 0.03 seconds.
Worked example 2 — Fuse clearing time computed from TCC table and arcing-current adjustment
Scenario:- System voltage: 480 V three-phase.
- Available bolted-fault current at fault location: Ibf = 12,000 A (12 kA).
- Protective device: Type gG HRC fuse rated 200 A located at the panel feeding the bus where arc occurs.
- We will estimate arcing current using a conservative reduction factor and then use a typical fuse TCC table to find clearing time.
- Using IEEE 1584 methodology would be preferred; for this illustrative calculation assume Iarc = 0.6 × Ibf for enclosed low-voltage conditions (typical empirical reduction factor range 0.5–0.9 depending on geometry).
- Compute: Iarc = 0.6 × 12,000 = 7,200 A.
- Multiple = Iarc / Irated = 7,200 / 200 = 36×.
| Multiple (I/Irated) | Typical fuse clearing time (s) |
|---|---|
| 10× | ≈0.5–1.0 |
| 20× | ≈0.05–0.2 |
| 30× | ≈0.02–0.08 |
| 40× | ≈0.01–0.03 |
| 50–100× | ≈0.005–0.02 |
- For multiple 36×, we interpolate between 30× and 40× giving typical clearing time ≈ 0.015–0.05 s; take a mid-range estimate ≈ 0.02 s.
Clearing time t_clear ≈ 0.02 s (approx). This value should be used as arc duration for incident energy calculation unless more precise manufacturer data or IEEE 1584 arcing current calculations are provided.
Alternative approach — analytic fit inversion
If the fuse manufacturer provides an analytic fit in the form t = A*(I/Irated)B:t = A * (I / Irated)B
Using illustrative constants A = 1.5, B = -3.0 (as an example):- t = 1.5 * (36)-3.0 = 1.5 * (36)-3 = 1.5 / (36^3) = 1.5 / 46656 ≈ 3.21 × 10-5 s (0.000032 s) — this demonstrates how sensitive exponent choice is and why analytic constants must come from manufacturer fits. This particular fit is not realistic for all fuse types; use manufacturer coefficients.
Considerations for multi-device systems and coordination
When multiple devices can clear a fault, arc duration equals the earliest operation among them. Therefore:- Calculate t_clear for all downstream and upstream protective devices using the same fault current basis (Iarc or Ibf consistent across devices).
- The device that trips first determines arc extinction. Check that protective coordination does not intentionally delay the upstream device such that the downstream device clears first.
- If reclosing occurs (automatic reclosers) ensure arc flash calculations consider reclose sequences and dead-time where appropriate.
Standards, authoritative references, and further reading
For professional practice and regulatory compliance consult the following authoritative sources:- IEEE 1584-2018: "IEEE Guide for Performing Arc-Flash Hazard Calculations" — provides methods for arcing current and incident energy estimation. https://standards.ieee.org/standard/1584-2018.html
- NFPA 70E: Standard for Electrical Safety in the Workplace — incident energy thresholds, PPE, and safety-related work practices. https://www.nfpa.org/70E
- IEC 60909: Short-circuit currents in three-phase AC systems — essential for computing Ibf. https://www.iec.ch
- Manufacturer technical bulletins and time-current curves — e.g., ABB, Schneider Electric, Eaton, Siemens provide validated TCC charts and digital files for modeling.
- IEEE C37 series and ANSI/IEEE relay curve families for understanding relay inverse-time equations.
Validation, uncertainty, and recommended best practices
Best practices to ensure safe, defensible calculations:- Always source TCC data from the protective device manufacturer. Do not rely solely on generic approximations for safety-critical decisions.
- Document whether Iarc or Ibf is used in the calculation and the method used to derive Iarc (IEEE 1584 or other).
- Perform sensitivity analyses on device settings (pickup, TMS, instantaneous threshold) and arcing current estimation to understand variability in t_clear and incident energy.
- Use log-log interpolation for tabular TCC data to maintain characteristic slopes across decades of current and time.
- Maintain conservative assumptions where required by safety policy (e.g., assume arcing current equals bolted-fault current if data is insufficient for a realistic reduction factor).
Summary of algorithmic checklist for an instant arc flash clearing time calculator
- Input: system topology, impedances, voltage, protective device settings/TCC.
- Compute Ibf using network short-circuit method (IEC 60909 or equivalent).
- Compute Iarc if using IEEE 1584 methodology; else decide on current basis.
- For each protective device: evaluate TCC at the chosen current using manufacturer table or analytic model to obtain t_candidate.
- Select t_clear = min(t_candidate) across devices capable of fault clearing at the location.
- Use t_clear as arc duration input for incident energy calculation (NFPA 70E / IEEE 1584).
- Document assumptions, sources, and any interpolation/fitting approaches.
Useful external authoritative links
- IEEE 1584-2018 Guide: https://standards.ieee.org/standard/1584-2018.html
- NFPA 70E information: https://www.nfpa.org/70E
- IEC standards search (60909): https://www.iec.ch/
- U.S. Occupational Safety and Health Administration (OSHA) electrical safety information: https://www.osha.gov/electrical