Voltage Drop Calculator

Calculate voltage drop in volts and percent for DC, single-phase and balanced three-phase circuits. Enter cable area, current, one-way length and conductor temperature. The result is an engineering estimate under the assumptions below.

Calculate voltage drop

Use a decimal point or comma. A single separator is treated as decimal: write 1000 for one thousand.

Use line-to-line voltage for balanced three-phase AC.
Source to load; do not double the distance.
The entered length is interpreted in the selected unit.
Current in one line conductor.
Greater than 0 and no greater than 1.
Select an area or enter a custom value. This does not select ampacity.
Area of one conductor, not the sum of all conductors.
Example value. Use cable data for your arrangement and frequency.
Conductor temperature, not ambient temperature. Supported calculation range: −20 to 120°C.
Your comparison target; this is not a universal code requirement.

Upload a datasheet plate or single-line diagram image to suggest conductor values and parameters.

Verify suggested values against your source document before relying on a calculation.

Compare cable scenarios

Calculate an option, save it, then change the inputs and save another. Compare up to three snapshots with their assumptions.

No scenarios saved yet. Comparisons stay in this tab until you reload.

Cable planning: choose your next check

Use ampacity and voltage drop as separate checks. Choose the tool for the information you have; review each model before using its result.

How to calculate voltage drop

  1. Select DC, single-phase AC or balanced three-phase AC. For three-phase, enter line-to-line voltage and line current.
  2. Enter the distance from the source to the load once. Choose metres or feet; do not add the return length.
  3. Select copper or aluminum and the area of one conductor. AWG entries are approximate geometric areas, not current ratings.
  4. Enter the conductor’s operating temperature. Ambient air temperature alone does not determine it.
  5. For AC, enter a lagging power factor and reactance for the cable arrangement and frequency. Zero reactance explicitly requests a resistance-only approximation.
  6. Set your project voltage-drop target and calculate. Read both the percentage and the assumptions.

Voltage drop formulas

With current I in amperes, one-way length L in kilometres, and per-conductor resistance R and reactance X in Ω/km:

CircuitApproximate voltage drop ΔV
DC, two conductors2 × I × L × R
Single-phase AC, two conductors2 × I × L × (R × PF + X × √(1 − PF²))
Balanced three-phase AC√3 × I × L × (R × PF + X × √(1 − PF²))

Percentage drop = 100 × ΔV / source voltage. The AC expressions estimate the longitudinal voltage change for a sinusoidal, lagging load. They are not the magnitude of the complete complex impedance drop. The DC and single-phase factors assume equal outgoing and return conductors. See the ELEK voltage-drop calculation guide for the AC model, and TxDOT’s explanation of one-way distance and loop resistance for the return-path distinction.

Resistance and temperature assumptions

This tool estimates resistance at 20°C as R20 = 17.24 / A for copper or 28.26 / A for aluminum, with A in mm² and R20 in Ω/km. It then uses R(T) = R20 × [1 + α × (T − 20)], with approximate coefficients α = 0.00393/°C and 0.00403/°C respectively. These ideal material estimates do not certify a particular cable; stranding, conductor class, alloy and AC effects can change the actual resistance.

The default X = 0.08 Ω/km is an illustrative input, not a value verified for your installation. Use cable manufacturer impedance data where available. For a three-phase calculation with your own R20, use the three-phase cable impedance calculator. Its copper reference presets can differ from the ideal-area estimates here.

Worked examples

These are arithmetic examples using the stated model; the conductor sizes are not installation recommendations.

InputsCalculationResult
24 V DC; 10 A; 10 m one-way; 10 mm² Cu; 20°C2 × 10 × 0.01 × 1.7240.3448 V; 1.44%; load voltage ≈ 23.66 V
230 V single-phase; 20 A; 50 m; 10 mm² Cu; 20°C; PF 1; X 02 × 20 × 0.05 × 1.7243.448 V; 1.50%; load voltage ≈ 226.55 V
Same single-phase inputs, conductor at 75°C3.448 × [1 + 0.00393 × 55]4.1932852 V; 1.82%

How to interpret the result

“Within target” refers only to the percentage you entered. The default 3% is a comparison setting, not a universal code limit. Check the equipment voltage range and the requirements applicable to your circuit. A small voltage drop does not establish ampacity, breaker suitability, terminal temperature rating, grounding or short-circuit protection.

For the same current and cable properties, twice the distance gives twice the calculated drop. Increasing conductor area reduces the resistive component; it does not automatically remove a reactive component. If the tool reports a large drop, fixed current and the AC approximation may no longer describe the actual operating point adequately.

Frequently asked questions

Should I double the cable length?

No. Enter source-to-load distance. This calculator applies the two-conductor factor or the balanced three-phase factor itself.

Why does the power factor affect the result?

When current is already known, the AC expression projects resistance and reactance using PF and √(1 − PF²). It does not divide the entire drop by PF. Calculating current from a known electrical kW input is a separate step.

Can I use a motor’s shaft kW?

First convert shaft output to electrical input using efficiency, or enter measured line current. The dedicated three-phase calculator explains the kW input convention.

Related: kW to amps · mm² to AWG.