Free NEC 220.84 Multifamily Load Calculator — Step-by-Step Feeder/Service Workflow
This article explains NEC 220 and Article 84 interpretation for multifamily load calculations and feeders.
Step-by-step methodology, free calculator workflow, feeder and service sizing, demand factors, and documentation NFPA guidance
NEC 220.84 Multifamily Feeder/Service Load Calculator (kVA and A)
NEC 220 and Article 84 framework for multifamily load calculations
NEC Article 220 defines methods to determine electrical load for services, feeders, and branch circuits. Article 84 provides definitions referenced by Article 220 that affect terminology such as "connected load," "general lighting load," and "appliance." For multifamily buildings the NEC provides several calculation methods, including unit-based and general-area methods, and specific demand factors and tables for ranges, dryers, HVAC, and other fixed appliances. Always confirm the jurisdictional edition of the NEC before final design.
This article provides a step-by-step feeder and service workflow that an engineer or designer can use with a free calculator or spreadsheet. It includes precise formulas, variable explanations with typical values, extensive tables of common appliance ratings and demand assumptions, and two fully developed real-world examples with detailed solutions. Links to authoritative sources and NEC references are included for verification.
Workflow overview: Feeder and service sizing process
Follow this ordered workflow to derive a compliant service/feeder size for multifamily dwellings:
Collect load data per unit and common areas (nameplate ratings, areas, HVAC types).
Classify loads: general lighting/receptacles, small appliance and laundry circuits, fixed appliances, heating/cooling, motors, elevators, common loads (corridors, mechanical rooms), and renewable systems or EV loads.
Tabulate connected loads and assign NEC-required minimum values (e.g., 1500 VA small appliance circuits).
Apply NEC demand factors and optional methods where permitted (per Article 220 tables and paragraphs).
Calculate feeder/service load using formulae, including diversity, largest motor contributions, and continuous loads 125% multiplier where applicable.
Select conductor ampacity and overcurrent protection based on load current and correction/ambient factors; check voltage drop and short-circuit coordination.
Document all assumptions, table references, and applied NEC sections for inspection and permitting.
Key formulas and variable definitions
Below are the primary calculation formulas used in the workflow. Each formula is presented with variable definitions and typical values:
Total Connected Load (sum of nameplate)
Total_Connected_Load = Σ P_i
Where:
P_i = nameplate power of load i in volt-amperes (VA) or watts (W). Typical values: small appliance circuit = 1500 VA, range = 8000–12000 W, dryer = 4800–6000 W, water heater = 4500 W.
Σ GL = sum of general lighting loads (VA), typically GL_area × area_ft2.
GL_area = lighting density, typical residential value = 3 VA/ft2.
Σ SA+LD = summed small appliance and laundry circuits (VA); usually 1500 VA per circuit × number of circuits.
DF_SA = demand factor applied to combined small appliance/laundry circuits per NEC or optional method (example values shown in tables below).
Σ FAP = sum of fixed appliance nameplate ratings (oven, dryer, water heater, etc.).
DF_FA = appliance demand factor per NEC tables or manufacturer data.
Σ HVAC = sum of HVAC loads (use nameplate or ASHRAE estimated heating/cooling wattage).
Σ Motors_effective = effective motor loads: apply locked-rotor or starting contributions as required for sizing switches and feeder short-time ratings; for continuous load sizing use running current.
Conversion to current (amperes)
I = Service_Load / V_phase_to_phase
Where:
I = design current in amperes (A).
Service_Load = total VA load (see formula above).
V_phase_to_phase = system voltage; typical values: 120/240 V single-phase = use 240 V for two-hot calculations; 208Y/120 V three-phase = use 208 V.
Continuous load adjustment (NEC requirement)
If any portion of the load is continuous (operating ≥ 3 hours), apply 125%:
Adjusted_Continuous_Load = 1.25 × Continuous_Component
Then include in Service_Load sum.
I_noncontinuous = current from non-continuous loads.
I_continuous = current from continuous loads (before 1.25 adjustment).
Voltage drop check (recommended limit)
VD% = (2 × L × I × R_conductor) / (V_service) × 100
Where:
VD% = percent voltage drop.
L = one-way conductor length in feet.
I = load current in amperes.
R_conductor = DC resistance per foot of conductor at 75°C (ohms/ft), selected from conductor tables.
V_service = nominal voltage (e.g., 120 V for single-phase branch, 240 V for feeder phase-to-phase).
Acceptable targets: design for VD% ≤ 3% for feeders to branch circuits, ≤ 5% total for feeder + branch.
Extensive tables of common values and demand assumptions
Item
Typical Nameplate Power (W or VA)
NEC Typical Assumption / Note
General lighting density (dwellings)
3 VA/ft2
Use local adopted NEC edition; 3 VA/ft2 commonly used for residences
Small appliance circuit
1500 VA per circuit
NEC minimum: two or more circuits per dwelling unit
Laundry circuit
1500 VA
Often required as a dedicated 20 A circuit
Electric range
8000 – 12000 W
Nameplate varies; apply NEC demand factors for multiple ranges
Electric dryer
4800 – 6000 W
Typical 5000 W nameplate for design
Electric water heater
3000 – 4500 W
4500 W common for 240 V residential tank heaters
Dishwasher
1200 – 1800 W
Design 1500 W typical
Garbage disposal
500 W
Typical motor-rated value
Refrigerator
600 – 1200 W (running)
Design 800 W running; motors add starting currents for coordination
HVAC (package heat pump, per unit)
2000 – 6000 W (electric heat) / 2000 – 6000 W compressor
Nameplate and manufacturer data required; consider largest motor starting current
EV charger (Level 2)
3.3 kW – 11 kW
Apply NEC 625 and local demand guidance; diversity often allowed with simultaneous use assumptions
Demand Factor Example Table (illustrative)
Applies to
Typical DF
First 1–3 units
Small appliance + laundry combined
100% for initial unit, then tapered per NEC optional method
Multiples of identical appliances
Ranges, dryers
Use NEC table values; example DF for multiple ranges reduces total below simple sum
Common area lighting
Corridors, stairwells
Calculate by area × lighting density; no dwelling unit diversity
Elevators
Motive power
Use manufacturer data and treat as motor load; may be non-continuous
Note: The second table provides illustrative demand-factor categories. For mandatory design values use the specific NEC edition tables (Article 220 and referenced tables) adopted by the authority having jurisdiction.
Step-by-step calculation procedure for a free calculator or spreadsheet
Use this algorithm in a calculator:
Input building data: number of units, floor area per unit, common-area floor area, appliance counts per unit, HVAC type, water heater type.
Compute small appliance and laundry circuits: SA_total = 1500 VA × #SA_circuits_total; LD_total = 1500 VA × #laundry_circuits_total.
Sum fixed appliances per unit and common appliances; list nameplate rating for each.
Apply NEC demand factors: apply DF_SA, DF_FA, and any optional multifamily methods permitted. For appliances subject to specific NEC tables, consult table and apply values.
Sum all loads into Service_Load. Identify continuous components and sum separately for 125% multiplier.
Convert Service_Load to current with appropriate system voltage and phase configuration.
Apply conductor sizing rules: choose conductor with ampacity ≥ Required_Ampacity, apply correction factors for temperature/ambient, and check overcurrent device sizing rules (NEC 240.4 and 240.6 for standard OCPD increments).
Voltage drop analysis: calculate VD% and increase conductor size if VD% exceeds design target.
Document results, including NE C references for each applied factor and table.
Worked example 1: Four-unit multifamily building, single-phase 240 V service (detailed)
Project data (assumptions listed and used for calculation):
Number of dwelling units: 4 identical units.
Unit area: 900 ft2 each.
Common area (corridor, mechanical room): 400 ft2.
Per unit fixed appliances: range 8.4 kW nameplate, electric dryer 5.0 kW, water heater 4500 W.
Per unit small appliance circuits: 2 circuits at 1500 VA each; laundry: 1 circuit 1500 VA.
Lighting density: 3 VA/ft2 (residential typical).
Voltage: 240 V single-phase (two hot legs), service neutral and grounds not used for load VA conversion.
Assumed demand factor usage for this example: apply 35% demand on combined small appliance + laundry total for aggregate after first unit (illustrative; check NEC for adopted method).
Step 1 — General lighting:
Per unit GL = 900 ft2 × 3 VA/ft2 = 2700 VA
Total GL for units = 2700 × 4 = 10,800 VA
Common GL = 400 ft2 × 3 = 1200 VA
Σ GL = 10,800 + 1200 = 12,000 VA
Step 2 — Small appliance and laundry:
Per unit SA + LD = (2 × 1500) + 1500 = 4500 VA
For 4 units, connected SA+LD = 4 × 4500 = 18,000 VA
Apply illustrative demand: for multifamily the first unit 100% then 35% for remainder: DF example = 1.00 + 0.35 × (n_unit − 1)
Effective SA+LD = 4500 × [1 + 0.35 × 3] = 4500 × (1 + 1.05) = 4500 × 2.05 = 9225 VA per equivalent unit
For all units effective SA+LD_total = 9225 × 1 (since the multiplier already accounts for units) = 9225 VA (this technique collapses units into effective single-unit equivalent for illustration)
Alternatively, many designers compute: Effective_SA_total = 4500 + 3 × (4500 × 0.35) = 4500 + 3 × 1575 = 4500 + 4725 = 9225 VA — same result.
Step 3 — Fixed appliances (ranges, dryers, water heaters):
Per unit: range = 8400 W, dryer = 5000 W, water heater = 4500 W → total per unit = 17,900 W
Total connected for 4 units = 4 × 17,900 = 71,600 W
Apply appliance demand factor: if NEC table allows demand reduction for multiple ranges/dryers, apply accordingly. For this illustration, apply conservative DF_FA = 65% for combined fixed appliances (example assumption).
Assume water heaters and some lighting components are continuous for design purposes? For this example treat none as continuous except maybe corridors continuous lighting (1,200 VA). Only corridor lighting considered continuous.
Continuous_component = common GL = 1,200 VA
Continuous_adjustment = 1.25 × 1,200 = 1,500 VA; replace continuous part in total with adjusted value: 67,765 − 1,200 + 1,500 = 68,065 VA
Step 6 — Convert to current:
I_service = 68,065 VA / 240 V = 283.6 A
Step 7 — Feeder ampacity and OCPD selection:
Required ampacity = 283.6 A; choose next standard conductor and OCPD per NEC 240.6(A).
Typical selection: 350 A main with three 350 A fuses or circuit breaker (check conductor thermal ratings); or use parallel feeders if permitted.
Step 8 — Voltage drop check:
Assume feeder one-way length = 150 ft to the farthest unit distribution point, I = 284 A. Using an example conductor copper 600 kcmil R ≈ 0.000032 ohm/ft at 75°C (example value for demonstration), VD% = (2 × 150 × 284 × 0.000032) / 240 × 100 ≈ 1.14% (acceptable).
Documentation: Record all assumptions, applied DF values, NEC table references used (Article 220 and applicable tables for appliances), and verify with AHJ.
Worked example 2: Ten-unit multifamily building, three-phase 208Y/120 V service (detailed)
Project assumptions:
Number of units: 10
Unit area: 650 ft2
Common area: 1200 ft2 corridors and mechanical spaces
Per unit appliances: refrigerator 800 W, dishwasher 1500 W, electric range 10 kW (assumed nameplate for some units), dryer 5 kW in 4 of the units only.
Small appliance circuits: 2 per unit × 1500 VA; laundry circuit provided in all units (1 × 1500 VA).
HVAC: packaged heat pump for each unit with electric supplemental heat (design heating load per unit 3000 W supplemental).
Service voltage: 208Y/120 V three-phase.
Step 1 — General lighting:
Per unit GL = 650 × 3 = 1950 VA; units total = 1950 × 10 = 19,500 VA
Common GL = 1200 × 3 = 3,600 VA
Σ GL = 23,100 VA
Step 2 — Small appliance and laundry:
Per unit SA+LD = (2 × 1500) + 1500 = 4500 VA
Connected SA+LD = 4500 × 10 = 45,000 VA
Apply illustrative multifamily demand: first unit 100% then 35% for each additional: Effective_SA_total = 4500 + 9 × (0.35 × 4500) = 4500 + 9 × 1575 = 4500 + 14,175 = 18,675 VA
Step 3 — Fixed appliances and selective dryers:
Ranges: assume 6 units have electric range 10,000 W = 60,000 W connected
Dryers: 4 units have dryer 5,000 W = 20,000 W connected
Dishwashers: 10 × 1500 = 15,000 W connected
Refrigerators: 10 × 800 = 8,000 W connected
Water heaters: assume centralized gas water heater (electrical minimal) — ignore electric heater load for this example.
Total fixed connected = 60,000 + 20,000 + 15,000 + 8,000 = 103,000 W
Apply appliance demand factor assumptions: for ranges, use NEC table values where multiple ranges reduce sum; for this example apply DF_range = 0.75 (illustrative). For dryers DF_dryer = 0.50 (illustrative). For dishwashers/refrigerators, no reduction assumed beyond small motor diversity.
Per unit supplemental electric heat = 3,000 W × 10 = 30,000 W connected
Assume diversity for electric heating may be reduced if not all operate simultaneously; for conservative sizing treat as 100% unless diversity info available.
Continuous loads: assume HVAC supplemental heating is potentially continuous during cold weather — treat as continuous for 125% factor: Continuous_component = 30,000 VA
Adjust continuous = 1.25 × 30,000 = 37,500 VA
Total adjusted = 149,775 − 30,000 + 37,500 = 157,275 VA
Step 6 — Convert to three-phase current (line-to-line voltage 208 V):
Step 7 — Feeder selection and parallel conductors:
Required ampacity ≈ 437 A; common choices: use 600 kcmil copper or 750 kcmil aluminum per phase depending on derating; or use parallel feeders if allowed by NEC 310.10(G) and AHJ.
Consider temperature and ambient correction factors and conductor bundling which may increase required conductor size.
Step 8 — Voltage drop check:
Assume one-way length 200 ft, I = 437 A, conductor example 600 kcmil copper R ≈ 0.000020 ohm/ft (approx); VD% = (√3 × I × L × R) / V_line_to_line × 100 (for three-phase, single-run formula) ≈ (1.732 × 437 × 200 × 0.000020) / 208 × 100 ≈ 1.45% (acceptable).
Document all steps, applied NEC table numbers, and manufacturer data for the ranges, dryers, and HVAC units. Use this documented calculation for permit submission.
Regulatory references and authoritative links
NFPA 70, National Electrical Code (NEC), Article 220: Load Calculations — primary regulatory source for load and demand-factor methodology. For code queries consult the edition adopted by the authority having jurisdiction: https://www.nfpa.org/NEC
NEC Article 84 — Definitions, provides definitions for terms used in load calculations: https://www.nfpa.org/ (search Article 84 in the applicable NEC edition)
IAEI (International Association of Electrical Inspectors) technical articles and training on calculating dwelling-unit loads and multifamily services: https://www.iaei.org/
IEEE and NEMA provide guidance on conductor ampacity, motor starting, and power system coordination: https://www.ieee.org/ and https://www.nema.org/
US Department of Energy: guidance on residential electrification and appliance typical loads: https://www.energy.gov/
When preparing final drawings and calculations, always cite the exact NEC edition and table numbers used, and upload manufacturer nameplate data as supporting documentation.
Practical considerations, common pitfalls, and QA checklist
Confirm jurisdictional NEC edition and any local amendments; demand factors may differ between editions or local amendments.
Always use actual nameplate ratings for appliances and HVAC equipment; do not substitute estimated values unless noted and approved.
Account for continuous loads with the 125% requirement in feeder and OCPD sizing.
Include motor starting currents and potential inrush when selecting overcurrent devices and evaluating voltage drop or feeder voltage regulation impact on HVAC and sensitive electronics.
Document every applied demand factor: reference the NEC paragraph/table and the reason for choosing optional methods.
Verify conductor ampacity adjustments for ambient temperature, raceway fill, and bundling per the NEC ampacity correction factors.
Plan for load growth, EV charging infrastructure, and potential future conversions; provide spare capacity or design for parallel feeders with space for future conductors.
How to implement this workflow in a free calculator or spreadsheet
Key features to include in a free load-calculator UI or spreadsheet:
Input form for unit counts, areas, and per-unit equipment counts with nameplate fields.
Auto-populate typical VA values from an internal library with editable fields for conservative or manufacturer-specific values.
Selection dropdown for NEC edition to toggle applicable demand factor tables (user must supply tables or reference manual updates).
Separate summation fields for continuous vs non-continuous loads and an automatic 125% multiplier for continuous parts.
Phase selection (single-phase or three-phase) and automatic conversion to line currents.
Conductor ampacity lookup and derating tables, including ambient and grouping factors.
Voltage drop calculator with recommended conductor minimums to meet specified VD% limits.
Exportable calculation report that cites NEC sections, tables, and lists input assumptions and nameplate attachments.
Record-keeping and submission documentation
Provide the AHJ and project stakeholders a calculation package including:
Single-line riser diagram with feeder conductor sizes, OCPD ratings, and grounding details.
Load calculation spreadsheet printout with itemized connected loads, applied demand factors, and all formula steps.
Nameplate copies for all significant appliances, HVAC units, and variable-speed drives.
Voltage drop calculations and conductor ampacity tables used.
References to NEC Article 220, Article 84 definitions, and any other applied NEC articles (motors, feeders, overcurrent protection).
Final engineering notes and compliance reminders
- The exact demand-factor application and permissible optional methods are edition-dependent; verify the NEC tables and paragraph numbers in the code edition governing the project.
- Where manufacturer data differs materially from assumed values, use the manufacturer data and document the change.
- For large multifamily projects consider diversity based on measured usage data from similar buildings or utility load profiles, and coordinate with the utility on service transformer sizing and service-point protections.
References (authoritative):
NFPA 70, National Electrical Code (NEC). NFPA. https://www.nfpa.org/NEC
International Association of Electrical Inspectors: technical resources for load calculation and inspection practices. https://www.iaei.org/
U.S. Department of Energy — Residential Building Electrification Guidance and appliance loads. https://www.energy.gov/
NEMA — conductor and equipment standards. https://www.nema.org/
If you want, I can produce a ready-to-use spreadsheet template implementing this exact workflow, pre-populated with the example data and formulas so you can run alternative scenarios rapidly.Free Nec 220 84 Multifamily Load Calculator Step By Step Feeder Service Workflow Guide