VA to Amp Converter: Must-Have Best Formula & Table

This technical guide explains converting volt-ampere (VA) to amperes for AC and DC applications accurately.

Essential formulas, tables, and worked examples ensure correct current sizing for single-phase and three-phase systems.

VA-to-Amp Converter — Best Formula Reference and Quick Presets

Upload a nameplate photo or wiring diagram to suggest nominal values for VA, voltage and power factor.

Please enter input values to display the computed current (A).
Formulas used
- For single-phase: I (A) = S (VA) / V (V) — units: A = VA / V.
- For three-phase (balanced, line-to-line): I (A) = S (VA) / (√3 × V (V)) — units: A = VA / (√3·V).
- When input provided is active power (P in W): S (VA) = P (W) / PF (unitless).
Notes: S is apparent power in VA, PF is power factor (cosφ), V is line voltage (V). (IEC/IEEE/NEC)
ApplicationTypical VANominal VApprox. I (A) @ single-phase
Desktop server600 VA230 V2.61 A
Small motor3000 VA400 V (3φ)4.33 A (per phase)
Lighting circuit2000 VA240 V8.33 A
UPS 5 kVA5000 VA230 V21.74 A
Frequently asked questions

Q: Should I use VA or W for current sizing?

A: Use VA (apparent power) for conductor or breaker sizing when the power factor is unknown. If you have active power (W) and PF, convert to VA = W / PF before computing current. (IEC/NEC)

Q: Which formula for three-phase systems?

A: For balanced three-phase networks use I = S / (√3·V_line-to-line). That assumes S is total three-phase apparent power in VA and V is line-to-line nominal voltage. (IEEE/IEC)

Fundamental Concepts: Apparent Power, Real Power, and Current

Understanding the conversion from VA to amps requires precise definitions:

  • Apparent power (S) measured in volt-amperes (VA) represents the product of RMS voltage and RMS current without regard to phase angle.
  • Real or active power (P) measured in watts (W) is the portion of apparent power performing useful work; P = S × PF.
  • Power factor (PF) is the cosine of the phase angle between voltage and current; PF ∈ (0, 1] for most industrial loads.
  • Current (I) in amperes (A) is the electrical quantity we compute from VA given voltage and system configuration (single-phase vs three-phase).

Core Conversion Formulas

Below are the essential formulas used to convert apparent power (VA) into current (A) for common wiring scenarios.

Va To Amp Converter Must Have Best Formula Table for Accurate Calculations
Va To Amp Converter Must Have Best Formula Table for Accurate Calculations

Single-phase AC or DC (general apparent power)

Formula: I = S / V

  • S = apparent power in VA (or kVA × 1000).
  • V = line-to-neutral or DC voltage in volts (V).
  • I = current in amperes (A).

Typical values: V = 120 V (North America residential), V = 230 V (IEC standard), V = 240 V (some regions and appliances).

Single-phase using real power and power factor

Formula: I = P / (V × PF)

  • P = real power in watts (W).
  • PF = power factor (unitless, commonly 0.8–1.0 for many loads).
  • Use this when only active power is specified or for energy billing alignment.

Three-phase balanced system (line-to-line voltage)

Formula: I = S / (√3 × V)

  • S = apparent power in VA (for three-phase total, not per phase).
  • V = line-to-line voltage in volts (V), e.g., 208 V, 400 V, 415 V, 480 V.
  • √3 ≈ 1.732. Alternatively use 1.732 × V in the denominator for numeric computation.
  • I = line current in amperes (A).

Three-phase using real power and power factor

Formula: I = P / (√3 × V × PF)

  • P = total real power in watts (W).
  • PF = power factor; include motor slip or correction factors when appropriate.

Variable Definitions and Typical Ranges

  • S (VA): Apparent power; common device nameplate values range from tens of VA (small electronics) to hundreds of kVA (transformers).
  • P (W): Active power; typical loads: lighting (10–100 W per fixture), HVAC compressors (several kW), industrial motors (several kW to MW).
  • V (V): System voltage; residential: 120/240 V, international single-phase: 230 V, three-phase industrial: 208 V, 400–415 V, 480 V, 690 V.
  • I (A): Current; wiring and protective devices are sized based on I with safety factors and codes applied.
  • PF (unitless): Power factor; resistive heaters PF ~1.0, induction motors PF 0.7–0.95 depending on load and correction.

Extensive Lookup Table — Single-phase VA to Amps

The following table lists common apparent power values and computed currents for widely used single-phase voltages. Use this as a quick VA-to-amp converter reference.

Apparent Power (VA) Current @ 120 V (A) Current @ 230 V (A) Current @ 240 V (A)
1000.8330.4350.417
5004.1672.1742.083
1,000 (1 kVA)8.3334.3484.167
2,000 (2 kVA)16.6678.6968.333
3,000 (3 kVA)25.00013.04312.500
5,000 (5 kVA)41.66721.73920.833
10,000 (10 kVA)83.33343.47841.667
15,000 (15 kVA)125.00065.21762.500
20,000 (20 kVA)166.66786.95783.333
30,000 (30 kVA)250.000130.435125.000
50,000 (50 kVA)416.667217.391208.333

Extensive Lookup Table — Three-phase VA to Amps

For three-phase balanced systems, currents are lower for the same VA due to the √3 factor. Table lists currents for common line voltages.

Apparent Power (kVA) Current @ 208 V (A) Current @ 400 V (A) Current @ 415 V (A) Current @ 480 V (A)
1 kVA2.7761.4431.3911.203
5 kVA13.8797.2136.9556.014
10 kVA27.75814.42613.90912.028
25 kVA69.39536.06434.77330.069
50 kVA138.78972.12869.54660.139
100 kVA277.579144.255139.092120.278
200 kVA555.158288.510278.183240.556

Detailed Worked Example 1 — Single-phase Residential Load

Case: A 240 V electric water heater rated 3,600 W (resistive). Determine the current draw and recommended breaker sizing.

  1. Identify given data:
    • P = 3,600 W (resistive, thus PF ≈ 1.0).
    • V = 240 V (single-phase).
  2. Select formula: For resistive load with PF = 1, use I = P / (V × PF) = P / V.
  3. Compute:
    • I = 3,600 W / 240 V = 15.0 A.
  4. Code and safety margin:
    • NEC continuous load rule: if the load is continuous (defined as 3 hours or more), size branch-circuit conductor and breaker at 125% of full-load current: 15.0 A × 1.25 = 18.75 A.
    • Round up to the next standard breaker size: 20 A.
    • Choose conductor ampacity accordingly (12 AWG typical for 20 A in many jurisdictions, consult local code and derating factors).
  5. Result: The heater draws 15.0 A; a 20 A breaker and 12 AWG conductor are typical if continuous load rules allow.

Detailed Worked Example 2 — Three-phase Industrial Motor Load

Case: A three-phase motor nameplate lists 50 kVA apparent power at 400 V line-to-line and PF = 0.9. Determine line current and conductor considerations.

  1. Given:
    • S = 50 kVA = 50,000 VA (apparent power).
    • V = 400 V (line-to-line).
    • PF = 0.9 (from nameplate).
  2. Choose formula for three-phase apparent power to current:
    • I = S / (√3 × V)
  3. Compute denominator:
    • √3 × V = 1.732 × 400 V = 692.8 V.
  4. Compute current using S:
    • I = 50,000 VA / 692.8 = 72.129 A (line current based on apparent power).
  5. If only real power P were given, P = S × PF = 50,000 × 0.9 = 45,000 W. The current using P and PF would be:
    • I = P / (√3 × V × PF) = 45,000 / (692.8 × 0.9) = 45,000 / 623.52 ≈ 72.129 A (same result, consistent).
  6. Apply code and thermal considerations:
    • Motors often have inrush currents many times full-load current; protective device selection must consider locked-rotor currents and motor-starting characteristics per IEEE and IEC guidance.
    • For continuous duty if applicable, apply 125% factor: 72.129 × 1.25 = 90.161 A. Choose next standard breaker/trip rating and conductor ampacity accordingly.
  7. Result: Line current ≈ 72.13 A; account for starting currents and apply code-required multipliers for conductor and protection sizing.

Worked Example 3 — UPS Sizing for Mixed Loads (added practical complexity)

Case: Data center rack draws 12 kW at 230 V single-phase with an aggregated PF of 0.95. Determine required UPS VA rating and input current.

  1. Given:
    • P = 12,000 W.
    • V = 230 V.
    • PF = 0.95.
  2. Compute required apparent power S = P / PF:
    • S = 12,000 / 0.95 = 12,631.58 VA ≈ 12.632 kVA.
  3. Compute input current on single-phase:
    • I = S / V = 12,631.58 / 230 ≈ 54.92 A.
  4. Sizing decisions:
    • Specify UPS with at least 12.7 kVA capacity (prefer an increment to cover harmonics and future load growth; e.g., 15 kVA).
    • Breaker sizing: 54.92 A × 1.25 (continuous) = 68.65 A → select 70 A or 80 A protective device depending on local code and conductor ampacity.
  5. Result: Required UPS apparent rating ≈ 12.7 kVA, input current ≈ 54.9 A; select protective devices per continuous-load rules and manufacturer recommendations.

Practical Considerations for Accurate Conversion

  • Always confirm whether the nameplate value is VA (apparent) or W (active). Misinterpreting the quantity is a common error.
  • Check whether voltage listed is line-to-line or line-to-neutral when dealing with three-phase systems; using the wrong voltage leads to 1.732× error.
  • Power factor matters: a low PF increases required current for the same real power and affects conductor heating and transformer loading.
  • Derating: account for ambient temperature, conductor bundling, altitude, and insulation temperature ratings when sizing conductors.
  • Motor starting and inrush: protective devices must allow safe starting; consider time-delay fuses, motor-starter curves, or soft starters.
  • Harmonics: nonlinear loads increase RMS current without increasing real power; include harmonic distortion factors when calculating thermal stress.
  • Measurement: use true-RMS meters and power analyzers for accurate measurement of VA and PF in non-sinusoidal systems.

Standards, Codes, and Authoritative References

Designers must apply recognized standards and local electrical codes when sizing equipment and protective devices. Key references include:

  • NFPA 70, National Electrical Code (NEC) — requirements for conductor ampacity, breakers, and continuous load rules. See https://www.nfpa.org/NEC
  • IEC 60364 — electrical installations of buildings; provides international wiring and safety guidance. See https://www.iec.ch/
  • IEC 60038 — standard voltages, useful for selecting nominal voltages for tables and calculations. See https://webstore.iec.ch/ (search IEC 60038)
  • IEEE Std 141 (Green Book) and IEEE Std 399 (Brown Book) — grounding, power system design, and industrial power considerations. See https://standards.ieee.org/
  • NIST publications and measurement guidance for electrical metrology and true-RMS measurements. See https://www.nist.gov/

Best Practice Checklist for VA to Amp Conversions

  1. Verify nameplate units: VA vs W.
  2. Determine system configuration: single-phase or three-phase and line voltage reference.
  3. Obtain or estimate power factor; if unknown, conservatively assume PF ≤ 0.9 for motors or mixed loads.
  4. Apply appropriate formula:
    • Single-phase: I = S / V or I = P / (V × PF).
    • Three-phase: I = S / (√3 × V) or I = P / (√3 × V × PF).
  5. Apply continuous-load multipliers and rounding rules from applicable codes.
  6. Consider inrush, harmonics, derating, and environmental factors for final conductor and protective device selection.
  7. Document assumptions and perform peer review or simulation for critical installations.

Measurement and Instrumentation Guidance

To validate calculations on-site, use the following tools and procedures:

  • True-RMS clamp meter to measure phase current accurately on non-sinusoidal loads.
  • Power quality analyzer to measure apparent power S, real power P, and PF simultaneously.
  • Verify voltages under load to use accurate V in calculations: measure line-to-line and line-to-neutral as required.
  • Record harmonic spectrum if loads include inverters, variable-frequency drives (VFDs), or switch-mode power supplies; high harmonics change heating characteristics.

SEO and Keyword Optimization Notes (embedded relevance)

Frequently searched queries addressed in this article include: "VA to amp converter", "convert VA to amps", "VA to A table", "VA to amp formula", "apparent power to current", "single-phase VA to amps", and "three-phase VA to amps". Use the lookup tables and worked examples to answer immediate practical needs and support keyword-rich long-form content for engineers and electricians.

Rounding, Units, and Reporting Recommendations

  • Report currents to three significant digits for engineering documentation; for procurement and breaker selection round up conservatively.
  • Always state whether currents are line currents or per-phase values when documenting three-phase systems.
  • When converting between kVA and VA, multiply kVA by 1,000. When converting between A and mA, multiply A by 1,000 as needed for instrumentation.
  • Include a margin for future load growth; industry practice often recommends 10–25% spare capacity depending on criticality.

Common Pitfalls and How to Avoid Them

  • Using line-to-neutral voltage for three-phase line-to-line calculations — results in a 1.732× error. Confirm voltage basis.
  • Ignoring power factor — underestimating current leads to undersized conductors and overheating risks.
  • Neglecting harmonics — harmonic currents increase RMS heating without increasing real power, requiring derating.
  • Failing to apply continuous-load multipliers from code — can result in overloaded breakers or conductors.

Final Engineering Reminder

VA-to-amp conversion is straightforward mathematically but requires careful attention to system configuration, power factor, harmonics, and applicable codes. Always document assumptions, verify on-site, and follow authoritative standards for protection and conductor sizing.

Selected Further Reading

  • NFPA 70 — National Electrical Code: https://www.nfpa.org/NEC
  • IEC Standards and publications: https://www.iec.ch/
  • IEEE Standards and recommended practices: https://standards.ieee.org/
  • NIST Electrical Measurement Guidance: https://www.nist.gov/
  • Technical overview on power factor and power relationships: https://www.energy.gov/ — search "power factor basics" for authoritative DOE materials.