Feeder Cable Sizing for Transformers Calculator – NEC

Correct feeder cable sizing for transformers is vital in electrical engineering, ensuring safe, efficient, and reliable operation. The NEC establishes precise requirements covering transformer conductors, overcurrent protection, and ampacity adjustments for consistent compliance.

Feeder Cable Sizing for Transformers — NEC (Quick Calculator)

Calculate transformer full-load currents (primary & secondary), minimum conductor ampacity and recommended OCPD sizes — based on kVA, voltage and phase. Use as a design aid; always verify with local code and a licensed electrician.

This tool uses standard kVA→A formulas and compares the required ampacity against common 75°C conductor ampacities. It does not replace a full code review — verify temperature ratings, derating, voltage drop and local amendments.
How is full-load current calculated?
Single-phase: I = 1000 × kVA / V. Three-phase: I = 1000 × kVA / (√3 × V).
Why 125% for continuous loads?
NEC requires conductor ampacity to be not less than 125% of continuous loads — this calculator multiplies by 1.25 when you mark the load as continuous.
Do you size the OCPD here?
The calculator proposes a nearest standard OCPD (breaker) size but final selection must respect NEC limits on overcurrent protection for conductor types and equipment terminals.

Why Feeder Cable Sizing Matters in Transformer Installations

Feeder conductors are responsible for carrying current between the main distribution system and transformer terminals. If undersized, cables can overheat, leading to insulation breakdown, voltage drop, fire hazards, or premature transformer failure. Oversizing cables, on the other hand, increases material costs and installation complexity.

Therefore, engineers must carefully balance ampacity requirements, overcurrent protection, temperature correction factors, and NEC compliance to ensure a reliable system.

Core NEC References for Transformer Feeder Cable Sizing

When designing transformer feeders, the following NEC Articles are most relevant:

  • Article 215 – Feeders
  • Article 240 – Overcurrent Protection
  • Article 250 – Grounding and Bonding
  • Article 310 – Conductors for General Wiring
  • Article 450 – Transformers and Transformer Vaults

Each article addresses different aspects such as conductor sizing, ampacity tables, protection methods, and grounding requirements.

Key Formulas for Transformer Feeder Cable Sizing

The following formulas are essential for determining feeder cable size according to NEC. Each variable is explained in detail with typical values.

1. Transformer Full-Load Current (FLC)

  • kVA = Transformer rating in kilovolt-amperes (commonly 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 2000).
  • V = System voltage (120, 208, 240, 277, 480, 600 V are typical in NEC systems).

2. Minimum Feeder Ampacity

  • Sf= Safety factor according to NEC. For transformer primary conductors, NEC requires at least 125% of the rated current (per NEC 450.3).

3. Voltage Drop Consideration

NEC recommends a maximum 3% voltage drop for feeders:

Where:

  • K = Resistivity constant (12.9 for copper, 21.2 for aluminum, at 75°C).
  • I = Load current (A).
  • L = One-way length of conductor (ft).
  • CM = Conductor circular mil area.

4. Conductor Ampacity Adjustment

From NEC 310.15(B)(2):

Extended NEC-Based Feeder Cable Sizing Tables

The following tables provide practical feeder sizing references. These are based on 75°C rated copper conductors using NEC 2023 ampacity tables, assuming typical transformer kVA ratings and voltages.

Table 1 – Full-Load Currents for Common Transformer Ratings (Three-Phase)

Transformer kVA208 V240 V480 V600 V
15 kVA42 A36 A18 A14 A
30 kVA83 A72 A36 A29 A
45 kVA125 A108 A54 A43 A
75 kVA208 A180 A90 A72 A
112.5 kVA312 A270 A135 A108 A
150 kVA416 A360 A180 A144 A
225 kVA625 A540 A270 A216 A
300 kVA833 A720 A360 A288 A
500 kVA1389 A1201 A601 A481 A
750 kVA2083 A1802 A902 A722 A
1000 kVA2778 A2402 A1203 A962 A

Table 2 – Minimum Feeder Ampacity (125% Rule)

Transformer kVA480 V FLC (A)Min Feeder Ampacity (125%)Suggested Feeder Conductor (Cu, 75°C)
45 kVA54 A68 A#4 AWG (85 A)
75 kVA90 A113 A#1 AWG (130 A)
112.5 kVA135 A169 A2/0 AWG (175 A)
150 kVA180 A225 A4/0 AWG (230 A)
225 kVA270 A338 A500 kcmil (380 A)
300 kVA360 A450 A600 kcmil (475 A)
500 kVA601 A751 A2 × 500 kcmil in parallel
750 kVA902 A1128 A3 × 500 kcmil in parallel
1000 kVA1203 A1504 A4 × 500 kcmil in parallel

Table 3 – Voltage Drop Factors for Common Conductor Sizes (Copper, 75°C)

Conductor Size (AWG/kcmil)Area (CM)Resistance (Ω/1000 ft)Voltage Drop (V/100 ft @ 100 A, 480 V)
#4 AWG417400.3213.2 V (0.7%)
#1 AWG836900.1261.3 V (0.3%)
2/0 AWG1331000.0780.8 V (0.2%)
4/0 AWG2116000.0490.5 V (0.1%)
500 kcmil5000000.0250.25 V (0.05%)
750 kcmil7500000.0170.17 V (0.04%)

Real-World Examples of Transformer Feeder Cable Sizing

Case 1 – 75 kVA, 480 V Three-Phase Transformer, 150 ft Feeder Run

Final Selection: #1 AWG copper, 75°C rated insulation.

Case 2 – 300 kVA, 480 V Three-Phase Transformer, 250 ft Feeder Run

Final Selection: 600 kcmil copper, 75°C rated insulation.

NEC Rules Governing Feeder Cable Sizing for Transformers

The National Electrical Code (NEC) does not only provide mathematical guidance but also sets practical rules for real-world installations. These rules ensure that conductor sizing is not just theoretical but applicable to installation conditions, environmental factors, and safety standards.

Here are the most relevant principles:

  1. Primary Side Conductor Sizing
    • Conductors supplying transformer primaries must be rated at at least 125% of the transformer’s rated primary current (NEC 450.3).
    • This ensures protection against overloads while allowing normal operating tolerances.
  2. Secondary Side Conductor Sizing
    • Secondary conductors must follow NEC 240.21(C), which provides special rules since secondary conductors are not always directly protected by OCPDs at their source.
    • Secondary conductors are sized based on length limitations, overcurrent protection location, and load requirements.
  3. Overcurrent Protection
    • Per NEC 240, the overcurrent protective device (OCPD) must protect conductors without exceeding their ampacity.
    • For transformers, this typically means a circuit breaker or fuse sized according to 125–250% of primary FLC, depending on transformer type and installation.
  4. Ampacity Adjustments and Corrections
    • Conductors installed in ambient temperatures above 30°C (86°F) must be derated per NEC 310.15.
    • Where more than three current-carrying conductors are in a raceway or cable, derating factors also apply.
    • This often leads engineers to select larger conductors than the theoretical calculation suggests.
  5. Voltage Drop Considerations
    • Although not strictly a code requirement, NEC recommends a maximum 3% voltage drop for feeders and 5% total for feeders plus branch circuits.
    • In large industrial installations, minimizing voltage drop improves efficiency and reduces energy costs.
  6. Parallel Conductors
    • For currents exceeding the largest standard conductor size (2000 kcmil), NEC allows parallel conductors.
    • Engineers often use multiple runs of 500 kcmil or 750 kcmil to carry very large transformer feeder currents.

Practical Tables for Common Transformer Feeders

Beyond formulas, engineers rely on lookup tables when selecting feeder cables. These tables allow quick decisions during design and installation.

Table 4 – Recommended Copper Feeder Sizes for Standard Transformers (480 V, 3-Phase, 75°C)

Transformer kVAFLC (A)Min Feeder Ampacity (125%)Typical Feeder Cable Size
15 kVA18 A23 A#10 AWG Cu (30 A)
30 kVA36 A45 A#8 AWG Cu (50 A)
45 kVA54 A68 A#4 AWG Cu (85 A)
75 kVA90 A113 A#1 AWG Cu (130 A)
112.5 kVA135 A169 A2/0 AWG Cu (175 A)
150 kVA180 A225 A4/0 AWG Cu (230 A)
225 kVA270 A338 A500 kcmil Cu (380 A)
300 kVA360 A450 A600 kcmil Cu (475 A)
500 kVA601 A751 A2 × 500 kcmil Cu (Parallel)
750 kVA902 A1128 A3 × 500 kcmil Cu (Parallel)
1000 kVA1203 A1504 A4 × 500 kcmil Cu (Parallel)

This table assumes copper conductors at 75°C. For aluminum, sizes increase by about two conductor sizes.

Real-World Engineering Considerations

Designing transformer feeders goes beyond calculations. Let’s look at critical engineering factors every professional considers.

1. Copper vs. Aluminum Conductors

  • Copper: Higher conductivity, smaller size, better mechanical strength, but more expensive.
  • Aluminum: Larger size required, more affordable, lighter, but needs special terminations and anti-oxidation treatment.
  • Common practice: Use copper for smaller feeders (<400 A) and aluminum for large feeders (>400 A) where cost savings are substantial.

2. Installation Environment

  • Conductors installed in underground conduits face higher ambient temperatures, requiring derating.
  • Outdoor feeders must account for UV exposure, moisture, and physical damage.
  • Industrial facilities often require special insulation types like XHHW-2 or THHN for durability.

3. Short-Circuit Withstand

  • Conductors must withstand fault currents until protective devices clear the fault.
  • For high kVA transformers, short-circuit currents can be extremely high, so proper coordination with OCPDs is critical.

4. Parallel Runs and Raceway Fill

  • Large feeders are often installed in parallel runs.
  • NEC requires equal length, same material, and same termination for each parallel conductor to ensure current sharing.
  • Raceway fill must also comply with NEC Chapter 9 to prevent overheating.

Example – Industrial Plant Transformer Feeder

Consider a 500 kVA transformer, 480 V, three-phase, feeding a motor control center located 200 ft away.

  1. Load Current: ~601 A (from tables).
  2. Minimum Feeder Ampacity: 751 A (125%).
  3. Feeder Selection: Two parallel sets of 500 kcmil copper (each rated 380 A) give 760 A capacity.
  4. Voltage Drop: At 200 ft, drop remains <2%, within NEC recommendations.
  5. Decision: Engineer chooses 2 × 500 kcmil Cu in parallel per phase, in separate conduits for easier pulling.

This design ensures NEC compliance, efficiency, and practical installation.

Advanced Example – Multiple Transformers in One Feeder System

In large commercial buildings, it is common to have several smaller transformers supplied from one main feeder. For example, three 75 kVA transformers on a common 480 V feeder.

  • Each transformer requires ~113 A feeder ampacity (after NEC factor).
  • The combined load = 3 × 113 A = 339 A.
  • Engineer sizes the main feeder at 400 A minimum, selecting 500 kcmil aluminum (430 A) to balance cost and performance.
  • Each transformer secondary still requires individual protection per NEC 240.21(C).

This approach highlights how system-level coordination is just as important as per-transformer sizing.