Cable Sizing by Current Calculator – NEC

Accurate cable sizing is critical for electrical safety, efficiency, and compliance with NEC standards. Calculating cable size by current ensures proper conductor selection.

This article explores the NEC guidelines, formulas, tables, and practical examples for cable sizing by current. Learn to optimize cable selection for real-world applications.

Artificial Intelligence (AI) Calculator for “Cable Sizing by Current Calculator – NEC”

  • ¡Hola! ¿En qué cálculo, conversión o pregunta puedo ayudarte?
Pensando ...
  • Calculate cable size for 100A, 3-phase, 480V copper conductor.
  • Determine conductor size for 50A single-phase, 240V aluminum cable.
  • Find cable size for 200A motor feeder, 600V, copper, 75°C insulation.
  • Calculate cable size for 30A lighting circuit, 120V, copper, 60°C rating.

Comprehensive Tables for Cable Sizing by Current – NEC Standards

The following tables summarize the most common conductor ampacities per NEC 2020, Article 310.15(B)(16), for copper and aluminum conductors with various insulation types and temperature ratings. These values assume ambient temperature of 30°C and conductors in raceways or cables.

Conductor Size (AWG/kcmil)Copper Ampacity (60°C)Copper Ampacity (75°C)Copper Ampacity (90°C)
14 AWG20 A25 A25 A
12 AWG25 A30 A30 A
10 AWG35 A40 A45 A
8 AWG50 A55 A60 A
6 AWG65 A75 A75 A
4 AWG85 A95 A100 A
3 AWG100 A115 A125 A
2 AWG115 A130 A145 A
1 AWG130 A150 A170 A
1/0 AWG150 A170 A195 A
2/0 AWG175 A195 A215 A
3/0 AWG200 A225 A240 A
4/0 AWG230 A260 A275 A

For aluminum conductors, ampacity values are generally lower due to higher resistivity and thermal characteristics. The following table lists typical aluminum conductor ampacities.

Conductor Size (AWG/kcmil)Aluminum Ampacity (60°C)Aluminum Ampacity (75°C)Aluminum Ampacity (90°C)
14 AWG15 A20 A20 A
12 AWG20 A25 A25 A
10 AWG25 A30 A35 A
8 AWG35 A40 A45 A
6 AWG40 A50 A55 A
4 AWG50 A65 A75 A
3 AWG55 A75 A85 A
2 AWG65 A90 A95 A
1 AWG75 A100 A110 A
1/0 AWG85 A115 A125 A
2/0 AWG95 A130 A145 A
3/0 AWG115 A150 A165 A
4/0 AWG130 A175 A195 A

Essential Formulas for Cable Sizing by Current According to NEC

Proper cable sizing requires understanding the relationship between current, voltage, conductor properties, and installation conditions. The NEC provides guidelines and formulas to calculate minimum conductor size.

1. Basic Current Carrying Capacity (Ampacity)

The ampacity of a conductor is the maximum current it can carry continuously without exceeding its temperature rating.

Formula:

I ≤ Ampacity
  • I: Load current (Amperes)
  • Ampacity: Maximum allowable current for the conductor size and insulation temperature rating (Amperes)

The conductor size must be selected so that its ampacity is equal to or greater than the load current.

2. Voltage Drop Calculation

Voltage drop affects system performance and must be limited, typically to 3% for feeders and branch circuits.

Formula:

Vd = (2 × K × I × L) / CM
  • Vd: Voltage drop (Volts)
  • K: Resistivity constant (Ohm-cmil/ft), typically 12.9 for copper, 21.2 for aluminum at 75°C
  • I: Load current (Amperes)
  • L: One-way length of the conductor (feet)
  • CM: Circular mil area of the conductor

For three-phase circuits, the factor 2 is replaced by √3 (~1.732).

3. Minimum Conductor Size Based on Load Current

Using the ampacity tables and applying correction factors for temperature and conduit fill, the minimum conductor size is selected.

Formula:

I_load ≤ Ampacity × Correction Factors
  • I_load: Load current (Amperes)
  • Correction Factors: Multiplicative factors for ambient temperature, conductor bundling, and insulation type (per NEC Table 310.15(B)(2)(a))

4. Conductor Cross-Sectional Area (Circular Mils)

To find the conductor size from ampacity or voltage drop, the circular mil area is calculated.

Formula:

CM = (2 × K × I × L) / Vd
  • CM: Circular mil area
  • Other variables as defined above

5. Adjusted Ampacity with Correction Factors

When multiple conductors are bundled or ambient temperature differs from 30°C, ampacity must be adjusted.

Formula:

I_adj = Ampacity × Temp_Correction × Bundling_Correction
  • I_adj: Adjusted ampacity
  • Temp_Correction: Temperature correction factor (NEC Table 310.15(B)(2)(a))
  • Bundling_Correction: Conductor bundling correction factor (NEC Table 310.15(C)(1))

Real-World Application Examples of Cable Sizing by Current – NEC

Example 1: Sizing a Copper Feeder Cable for a 100A Load at 480V 3-Phase

Problem Statement: Determine the minimum copper conductor size for a 100A, 480V, 3-phase feeder cable with THHN insulation rated at 75°C. The cable length is 150 feet. Ambient temperature is 30°C, and no bundling correction is needed.

Step 1: Determine Base Ampacity

From NEC Table 310.15(B)(16), copper conductor ampacity at 75°C:

  • 4 AWG = 95A
  • 3 AWG = 115A

Since 4 AWG (95A) is less than 100A load, select 3 AWG (115A) as minimum conductor size.

Step 2: Check Voltage Drop

Calculate voltage drop to ensure it is within 3% of 480V (14.4V max).

Using formula for 3-phase:

Vd = (√3 × K × I × L) / CM

Where:

  • K = 12.9 (copper at 75°C)
  • I = 100A
  • L = 150 ft
  • CM for 3 AWG copper = 52,620 circular mils

Calculate:

Vd = (1.732 × 12.9 × 100 × 150) / 52620 ≈ (335,034) / 52620 ≈ 6.37 V

Voltage drop is 6.37V, which is 1.33% of 480V, well below 3%. Therefore, 3 AWG copper conductor is acceptable.

Example 2: Sizing an Aluminum Branch Circuit for 50A, 240V Single-Phase Load

Problem Statement: Select the minimum aluminum conductor size for a 50A, 240V single-phase branch circuit. The cable length is 100 feet, THWN insulation rated at 75°C. Ambient temperature is 35°C, requiring temperature correction. Three current-carrying conductors are bundled.

Step 1: Base Ampacity Selection

From NEC Table 310.15(B)(16), aluminum ampacity at 75°C:

  • 8 AWG = 40A
  • 6 AWG = 50A
  • 4 AWG = 65A

6 AWG aluminum conductor has 50A ampacity, matching the load.

Step 2: Apply Temperature Correction Factor

From NEC Table 310.15(B)(2)(a), for 35°C ambient and 75°C insulation, correction factor ≈ 0.94.

Step 3: Apply Bundling Correction Factor

For 3 current-carrying conductors, correction factor from NEC Table 310.15(C)(1) is 1.0 (no reduction).

Step 4: Calculate Adjusted Ampacity

I_adj = 50A × 0.94 × 1.0 = 47A

Adjusted ampacity is 47A, which is less than 50A load. Therefore, 6 AWG is insufficient.

Step 5: Select Next Larger Size

Next size is 4 AWG aluminum with 65A ampacity.

Adjusted ampacity for 4 AWG:

I_adj = 65A × 0.94 × 1.0 = 61.1A

61.1A > 50A load, so 4 AWG aluminum conductor is acceptable.

Step 6: Check Voltage Drop

Calculate voltage drop for 4 AWG aluminum (CM = 83,690):

Vd = (2 × 21.2 × 50 × 100) / 83690 ≈ (212,000) / 83690 ≈ 2.53 V

Percentage voltage drop:

(2.53 V / 240 V) × 100% ≈ 1.05%

Voltage drop is within 3% limit, confirming 4 AWG aluminum conductor is suitable.

Additional Technical Considerations for NEC Cable Sizing

  • Ambient Temperature Correction: NEC requires ampacity adjustments for ambient temperatures above 30°C. Use Table 310.15(B)(2)(a) for correction factors.
  • Conductor Bundling: More than three current-carrying conductors in a raceway or cable require ampacity derating per NEC Table 310.15(C)(1).
  • Voltage Rating: Ensure conductor insulation voltage rating meets or exceeds system voltage.
  • Short-Circuit Rating: Verify conductor withstands short-circuit currents per NEC 110.10.
  • Grounding Conductors: Size grounding conductors per NEC Table 250.122, which differs from current-carrying conductor sizing.
  • Conductor Material: Copper offers better conductivity but higher cost; aluminum is lighter but requires larger sizes.
  • Insulation Types: THHN, THWN, XHHW, and others have different temperature ratings affecting ampacity.
  • Voltage Drop Limits: NEC recommends limiting voltage drop to 3% for feeders and branch circuits to maintain efficiency and equipment longevity.

For detailed NEC guidelines, consult the official NEC Handbook or NFPA website: NFPA NEC Resources.

Summary of Key NEC Tables for Cable Sizing

NEC TableDescriptionPurpose
310.15(B)(16)Conductor Ampacity TablesBase ampacity values for copper and aluminum conductors
310.15(B)(2)(a)Ambient Temperature Correction FactorsAdjust ampacity for ambient temperature variations
310.15(C)(1)Adjustment Factors for More Than Three ConductorsDerate ampacity for conductor bundling
250.122Equipment Grounding Conductor SizeMinimum grounding conductor sizes

Understanding and applying these tables and formulas ensures NEC-compliant, safe, and efficient cable sizing for electrical installations.