Primary and Secondary Protection Sizing According to NEC Calculator – NEC

Accurate primary and secondary protection sizing is critical for electrical system safety and compliance with NEC standards. Proper calculations prevent equipment damage and ensure reliable operation.

This article thoroughly explores NEC-based protection sizing, including formulas, tables, and real-world examples. Learn to apply NEC guidelines effectively for optimal protection device selection.

Artificial Intelligence (AI) Calculator for “Primary and Secondary Protection Sizing According to NEC Calculator – NEC”

  • ¡Hola! ¿En qué cálculo, conversión o pregunta puedo ayudarte?
Pensando ...
  • Calculate primary and secondary fuse sizes for a 480V, 200A transformer.
  • Determine secondary protection for a 75kVA, 208Y/120V transformer.
  • Find primary fuse rating for a 150kVA transformer with 600V primary voltage.
  • Compute secondary breaker size for a 112.5kVA transformer with 240V secondary voltage.

Comprehensive Tables for Primary and Secondary Protection Sizing According to NEC

Transformer kVA RatingPrimary Voltage (V)Primary Full Load Current (A)Primary Fuse Size (A) (NEC 450.3)Notes
1548018.125Standard fuse size, 125% of full load current
3048036.350Typical primary fuse rating
7548090.1125Fuse size per NEC 450.3(B)
112.5480135.1175Common primary fuse size
150480180.2225Fuse size rounded to next standard size
225480270.3350Large transformer primary protection
300480360.4400High capacity primary fuse
Transformer kVA RatingSecondary Voltage (V)Secondary Full Load Current (A)Secondary Overcurrent Device Size (A)Notes
15120/24062.580125% of full load current per NEC 450.3(B)
30120/240125150Standard breaker size
75208Y/120208250Secondary breaker size per NEC
112.5240468.8600Large secondary breaker
150240625700Breaker size rounded up

Table 3: Common Transformer Full Load Currents (FLC) for Various kVA and Voltages

Transformer kVAPrimary Voltage (V)Secondary Voltage (V)Primary FLC (A)Secondary FLC (A)
15480120/24018.162.5
30480120/24036.3125
75480208Y/12090.1208
112.5480240135.1468.8
150600240144.3625

Essential Formulas for Primary and Secondary Protection Sizing According to NEC

1. Transformer Full Load Current (FLC) Calculation

The fundamental starting point for protection sizing is calculating the transformer’s full load current on both primary and secondary sides.

Primary FLC (A) = Transformer kVA × 1000 / (√3 × Primary Voltage (V))
Secondary FLC (A) = Transformer kVA × 1000 / (√3 × Secondary Voltage (V))
  • Transformer kVA: Rated power of the transformer in kilovolt-amperes.
  • Primary Voltage (V): Rated primary voltage of the transformer.
  • Secondary Voltage (V): Rated secondary voltage of the transformer.
  • √3: Square root of 3 (~1.732), used for three-phase systems.

For single-phase transformers, the formula simplifies to:

FLC (A) = Transformer kVA × 1000 / Voltage (V)

2. Primary Protection Sizing (NEC 450.3(B))

NEC 450.3(B) provides guidelines for sizing primary overcurrent protection devices (OCPD) for transformers.

Primary OCPD Size (A) = Transformer Primary FLC × 125%
  • The 125% multiplier accounts for inrush current and transformer heating.
  • OCPD size must not exceed the next standard fuse or breaker size above this value.

3. Secondary Protection Sizing (NEC 450.3(B))

Secondary protection sizing also follows the 125% rule but must consider the transformer’s secondary full load current.

Secondary OCPD Size (A) = Transformer Secondary FLC × 125%
  • Secondary OCPD protects the transformer and downstream equipment.
  • Must be coordinated with primary protection to avoid nuisance tripping.

4. Maximum Primary OCPD Size (NEC 450.3(B))

NEC limits the maximum primary OCPD size to prevent excessive fault current.

Maximum Primary OCPD Size = Transformer kVA × 6.25
  • This ensures the primary fuse or breaker does not exceed a value that could damage the transformer.

5. Minimum Secondary OCPD Size (NEC 450.3(B))

NEC also specifies a minimum secondary OCPD size to avoid nuisance tripping during transformer energization.

Minimum Secondary OCPD Size = Transformer Secondary FLC × 125%

This is the same as the secondary protection sizing formula but serves as a minimum threshold.

Detailed Real-World Examples of Primary and Secondary Protection Sizing

Example 1: Sizing Protection for a 75 kVA, 480V/208Y/120V Transformer

Calculate the primary and secondary overcurrent protection device sizes for a 75 kVA three-phase transformer with a 480V primary and 208Y/120V secondary.

Step 1: Calculate Full Load Currents

Primary FLC:

Primary FLC = (75 × 1000) / (√3 × 480) = 75000 / 831.6 ≈ 90.1 A

Secondary FLC:

Secondary FLC = (75 × 1000) / (√3 × 208) = 75000 / 360.5 ≈ 208.1 A

Step 2: Calculate Primary OCPD Size

Primary OCPD = 90.1 × 1.25 = 112.6 A

Choose the next standard fuse size: 125 A.

Step 3: Verify Maximum Primary OCPD Size

Max Primary OCPD = 75 × 6.25 = 468.75 A

125 A is less than 468.75 A, so the fuse size is acceptable.

Step 4: Calculate Secondary OCPD Size

Secondary OCPD = 208.1 × 1.25 = 260.1 A

Choose the next standard breaker size: 275 A or 300 A (depending on availability).

Summary:

  • Primary fuse size: 125 A
  • Secondary breaker size: 275 A or 300 A

Example 2: Protection Sizing for a 150 kVA, 600V/240V Transformer

Determine the primary and secondary protection sizes for a 150 kVA transformer with a 600V primary and 240V secondary.

Step 1: Calculate Full Load Currents

Primary FLC:

Primary FLC = (150 × 1000) / (√3 × 600) = 150000 / 1039.2 ≈ 144.3 A

Secondary FLC:

Secondary FLC = (150 × 1000) / (√3 × 240) = 150000 / 415.7 ≈ 360.7 A

Step 2: Calculate Primary OCPD Size

Primary OCPD = 144.3 × 1.25 = 180.4 A

Next standard fuse size: 200 A or 225 A (225 A preferred for margin).

Step 3: Verify Maximum Primary OCPD Size

Max Primary OCPD = 150 × 6.25 = 937.5 A

225 A is well below 937.5 A, so acceptable.

Step 4: Calculate Secondary OCPD Size

Secondary OCPD = 360.7 × 1.25 = 450.9 A

Next standard breaker size: 475 A or 500 A.

Summary:

  • Primary fuse size: 225 A
  • Secondary breaker size: 475 A or 500 A

Additional Technical Considerations for NEC Protection Sizing

  • Inrush Current: Transformers draw a high inrush current during energization, often 6-12 times full load current. The 125% sizing factor helps accommodate this.
  • Coordination: Primary and secondary protection devices must be coordinated to ensure selective tripping and minimize system downtime.
  • NEC Exceptions: NEC 450.3(B) allows exceptions for certain transformer types or applications, such as transformers with integral primary protection.
  • Fuse Types: Time-delay fuses are preferred for transformer protection to handle inrush currents without nuisance tripping.
  • Voltage Ratings: Protection devices must be rated for the system voltage and interrupting capacity per NEC 110.9 and 240.60.
  • Temperature Ratings: Ambient temperature and conductor insulation ratings affect protection device sizing and must be considered.

Authoritative References and Further Reading

By following NEC guidelines and applying these calculations, engineers can ensure safe, reliable transformer protection. Proper sizing minimizes risk and optimizes system performance.