Surge Protective Devices (TVSS) Calculator – IEC, IEEE

Surge Protective Devices (SPDs), also known as Transient Voltage Surge Suppressors (TVSS), are critical for safeguarding electrical systems. Calculating their parameters ensures optimal protection against transient overvoltages.

This article explores SPD calculation methods based on IEC and IEEE standards, providing formulas, tables, and real-world examples. Engineers and technicians will gain comprehensive insights for precise SPD selection and application.

Artificial Intelligence (AI) Calculator for “Surge Protective Devices (TVSS) Calculator – IEC, IEEE”

  • ¡Hola! ¿En qué cálculo, conversión o pregunta puedo ayudarte?
Pensando ...
  • Calculate SPD nominal discharge current (In) for a 400 V system with 10 kA surge current.
  • Determine maximum continuous operating voltage (Uc) for a 230 V single-phase system.
  • Compute voltage protection level (Up) for a 3-phase 480 V system with 20 kA surge current.
  • Estimate total let-through energy (W) for a 100 kA surge current SPD.

Common Values for Surge Protective Devices (TVSS) – IEC and IEEE Standards

ParameterTypical ValuesUnitsDescription
Nominal Discharge Current (In)5, 10, 20, 40kA (8/20 µs waveform)Maximum current SPD can repeatedly conduct without damage
Maximum Continuous Operating Voltage (Uc)230, 400, 480, 600V AC or DCMaximum voltage SPD can continuously withstand without degradation
Voltage Protection Level (Up)600, 900, 1200, 1500VMaximum voltage let-through during surge event
Maximum Discharge Current (Imax)10, 20, 40, 100kA (8/20 µs waveform)Maximum surge current SPD can withstand once
Energy Rating (W)100, 200, 500, 1000kJTotal energy SPD can absorb during surge
Response Time<1, 10, 20nanoseconds (ns)Time taken to respond to surge event

IEC and IEEE Standards Relevant to SPD Calculations

StandardScopeKey ParametersReference
IEC 61643-11Low-voltage SPDs for AC power systemsIn, Imax, Up, UcIEC Webstore
IEEE C62.41.2Surge environment and surge protection in low-voltage AC power circuitsSurge waveforms, test currentsIEEE Standards
IEC 62305Protection against lightningLightning current parameters, risk assessmentIEC Webstore
IEEE C62.45Test methods for surge protective devicesTest waveforms, performance criteriaIEEE Standards

Essential Formulas for Surge Protective Devices (TVSS) Calculations

1. Nominal Discharge Current (In)

The nominal discharge current is the peak value of the current the SPD can repeatedly conduct without degradation.

In = Ipeak (8/20 µs waveform)
  • In: Nominal discharge current (kA)
  • Ipeak: Peak surge current (kA) with 8/20 µs waveform

2. Maximum Continuous Operating Voltage (Uc)

Uc is the maximum RMS voltage the SPD can continuously withstand without damage.

Uc ≥ Vnom
  • Uc: Maximum continuous operating voltage (V)
  • Vnom: Nominal system voltage (V)

3. Voltage Protection Level (Up)

Up is the maximum voltage the SPD allows to pass during a surge event, protecting downstream equipment.

Up = Vmax + (In × ZSPD)
  • Up: Voltage protection level (V)
  • Vmax: Maximum system voltage (V)
  • In: Nominal discharge current (kA)
  • ZSPD: Dynamic impedance of SPD (Ω)

4. Maximum Discharge Current (Imax)

Imax is the highest surge current the SPD can withstand once without failure.

Imax ≥ Imax surge
  • Imax: Maximum discharge current (kA)
  • Imax surge: Maximum expected surge current (kA)

5. Energy Absorption (W)

Energy rating indicates the total energy the SPD can absorb during surge events.

W = ∫ v(t) × i(t) dt (Joules or kJ)
  • W: Energy absorbed (J or kJ)
  • v(t): Voltage across SPD during surge (V)
  • i(t): Current through SPD during surge (A)

6. Let-Through Voltage Calculation

Let-through voltage is critical for ensuring downstream equipment safety.

Vlet-through = Up + (I × Zsystem)
  • Vlet-through: Voltage let-through (V)
  • I: Surge current (kA)
  • Zsystem: System impedance (Ω)

Real-World Application Examples of SPD Calculations

Example 1: Selecting an SPD for a 230 V Single-Phase Industrial Power System

An industrial facility operates a 230 V single-phase system. The expected surge current is 20 kA (8/20 µs waveform). The system impedance is 0.05 Ω. The SPD must protect sensitive equipment with a maximum withstand voltage of 1000 V.

  • Step 1: Determine Uc
  • Uc must be ≥ nominal voltage, so Uc ≥ 230 V. Select Uc = 275 V (standard value above nominal).

  • Step 2: Choose In
  • Nominal discharge current In should be at least 20 kA to handle expected surges.

  • Step 3: Calculate Up
  • Assuming SPD dynamic impedance ZSPD = 0.02 Ω:

    Up = Vmax + (In × ZSPD) = 230 + (20 × 0.02 × 1000) = 230 + 400 = 630 V

    Up = 630 V, which is below the equipment withstand voltage of 1000 V, so acceptable.

  • Step 4: Verify Imax
  • Select SPD with Imax ≥ 40 kA for safety margin.

  • Step 5: Energy rating
  • Choose SPD with energy rating W ≥ 200 kJ for durability.

Result: An SPD with Uc = 275 V, In = 20 kA, Up = 630 V, Imax = 40 kA, and W = 200 kJ is suitable.

Example 2: Calculating Let-Through Voltage for a 480 V Three-Phase System

A commercial building uses a 480 V three-phase system. The SPD nominal discharge current is 10 kA, system impedance is 0.1 Ω, and SPD voltage protection level is 900 V. Calculate the let-through voltage during a surge.

  • Step 1: Use the let-through voltage formula:
  • Vlet-through = Up + (I × Zsystem) = 900 + (10 × 0.1 × 1000) = 900 + 1000 = 1900 V

    Note: Current converted to amperes (10 kA = 10,000 A), so 10,000 × 0.1 Ω = 1000 V.

  • Step 2: Assess equipment withstand voltage
  • Ensure downstream equipment can tolerate 1900 V transient.

Result: The let-through voltage is 1900 V, so equipment must be rated accordingly or additional protection is needed.

Additional Technical Considerations for SPD Calculations

  • Waveform Selection: IEC and IEEE specify 8/20 µs and 10/350 µs waveforms for surge current testing. The 8/20 µs waveform simulates switching surges, while 10/350 µs simulates lightning impulses.
  • Coordination of SPDs: Multi-stage protection involves primary SPDs with high Imax and secondary SPDs with low Up to protect sensitive electronics.
  • Temperature Effects: SPD parameters vary with temperature; derating may be necessary in high-temperature environments.
  • System Grounding: Proper grounding reduces system impedance and improves SPD performance.
  • SPD Life Expectancy: Calculated based on cumulative energy absorption and number of surge events.

Summary of Key SPD Parameters and Their Impact

ParameterImpact on SystemDesign Considerations
Nominal Discharge Current (In)Determines SPD durability under repeated surgesSelect based on expected surge magnitude and frequency
Maximum Continuous Operating Voltage (Uc)Ensures SPD does not degrade under normal voltageMust be ≥ system nominal voltage
Voltage Protection Level (Up)Limits voltage stress on protected equipmentLower Up preferred for sensitive electronics
Maximum Discharge Current (Imax)Defines SPD’s ability to survive extreme surgesSelect with safety margin above maximum expected surge
Energy Rating (W)Indicates total energy absorption capacityHigher rating extends SPD service life

References and Further Reading