Short-Circuit Current Using Infinite Bus Method Calculator – IEEE, IEC

Short-circuit current calculation is critical for designing safe and reliable electrical power systems. It determines the maximum current flowing during faults, ensuring protective devices operate correctly.

This article explores the Infinite Bus Method for short-circuit current calculation, aligned with IEEE and IEC standards. It covers formulas, tables, and practical examples for engineers and technicians.

Artificial Intelligence (AI) Calculator for “Short-Circuit Current Using Infinite Bus Method Calculator – IEEE, IEC”

Download TXT
  • Calculate 3-phase short-circuit current for a 11 kV system with 10 MVA source and 10% impedance.
  • Determine symmetrical short-circuit current at 33 kV bus with 50 MVA transformer and 5% reactance.
  • Find the initial short-circuit current for a 415 V motor feeder with 2 MVA base and 8% impedance.
  • Compute the short-circuit current at 132 kV substation with 100 MVA generator and 12% reactance.

Common Values for Short-Circuit Current Using Infinite Bus Method – IEEE, IEC

ParameterTypical ValuesUnitsNotes
System Voltage (Line-to-Line)0.4, 11, 33, 66, 132, 220, 400kVCommon distribution and transmission voltages
Base Power (S_base)1, 5, 10, 50, 100, 500MVATypical transformer or generator ratings
Per Unit Impedance (Z_pu)0.05 to 0.15p.u.Transformer or generator reactance values
Short-Circuit Power (S_sc)500 to 5000MVAInfinite bus equivalent power
Short-Circuit Current (I_sc)1 to 50kACalculated symmetrical RMS current

Additional Typical Parameters for IEEE and IEC Standards

StandardParameterValue RangeDescription
IEEE Std 141X/R Ratio5 to 15Ratio of reactance to resistance for fault current calculation
IEC 60909Voltage Factor (c)1.0 to 1.1Voltage correction factor for short-circuit calculations
IEEE Std 399Transformer Impedance (Z_t)0.05 to 0.12 p.u.Typical transformer short-circuit impedance
IEC 60909Correction Factor for Motor Contribution1.0 to 1.5Multiplier for motor starting current in fault calculations

Fundamental Formulas for Short-Circuit Current Using Infinite Bus Method

The Infinite Bus Method assumes the power system is connected to an ideal voltage source with constant voltage and frequency, unaffected by faults. This simplifies short-circuit current calculations by treating the source as an infinite bus.

1. Base Short-Circuit Current Calculation

The symmetrical short-circuit current (I_sc) at the fault point is calculated by:

Isc = VLL / (√3 × Zsc)
  • Isc: Symmetrical short-circuit current (Amperes, A)
  • VLL: Line-to-line voltage at the fault point (Volts, V)
  • Zsc: Total equivalent impedance seen from the fault point (Ohms, Ω)

The total impedance Zsc includes source, transformer, line, and load impedances, converted to a common base.

2. Per Unit Impedance Conversion

To unify impedances from different equipment, convert to per unit (p.u.) values on a common base:

Znew = Zold × (Sbase / Sold)
  • Znew: Impedance on new base (p.u.)
  • Zold: Original impedance (p.u.)
  • Sbase: New base power (MVA)
  • Sold: Original base power (MVA)

3. Short-Circuit Current in kA

Using the system base values, the short-circuit current can be expressed as:

Isc = (Sbase × 103) / (√3 × VLL × Zpu)
  • Isc: Short-circuit current (Amperes, A)
  • Sbase: Base apparent power (MVA)
  • VLL: Line-to-line voltage (Volts, V)
  • Zpu: Per unit impedance at fault point (p.u.)

4. Infinite Bus Equivalent Impedance

The infinite bus is modeled as a voltage source with an internal impedance:

Zbus = Vbase2 / Ssc
  • Zbus: Equivalent bus impedance (Ohms, Ω)
  • Vbase: Base voltage (Volts, V)
  • Ssc: Short-circuit power (VA)

5. Correction Factors per IEC 60909

IEC 60909 recommends applying voltage and correction factors to account for operating conditions:

Ik = (c × Un) / (√3 × Zk)
  • Ik: Short-circuit current (A)
  • c: Voltage factor (1.0 to 1.1)
  • Un: Nominal system voltage (V)
  • Zk: Equivalent short-circuit impedance (Ω)

Detailed Real-World Examples

Example 1: Calculating 3-Phase Short-Circuit Current at 11 kV Bus

A power system has a 10 MVA transformer rated at 11 kV with 10% impedance. Calculate the symmetrical short-circuit current at the transformer secondary bus using the Infinite Bus Method.

Given Data:

  • Transformer rating, Sbase = 10 MVA
  • System voltage, VLL = 11 kV
  • Transformer impedance, Zpu = 0.10 p.u.

Step 1: Calculate base current

Ibase = Sbase × 103 / (√3 × VLL) = (10 × 103) / (1.732 × 11 × 103) = 525.7 A

Step 2: Calculate short-circuit current

Isc = Ibase / Zpu = 525.7 / 0.10 = 5257 A = 5.257 kA

The symmetrical short-circuit current at the 11 kV bus is approximately 5.26 kA.

Example 2: Short-Circuit Current at 33 kV Bus with Multiple Sources

Consider a 33 kV bus fed by a 50 MVA generator with 8% reactance and a 100 MVA infinite bus with short-circuit power of 2000 MVA. Calculate the total symmetrical short-circuit current at the bus.

Given Data:

  • Generator rating, Sgen = 50 MVA
  • Generator reactance, Xgen = 0.08 p.u.
  • Infinite bus short-circuit power, Ssc = 2000 MVA
  • System voltage, VLL = 33 kV

Step 1: Calculate generator impedance in ohms

Zgen = Vbase2 / Sbase × Xgen = (33,000)2 / (50 × 106) × 0.08 = 1.742 Ω

Step 2: Calculate infinite bus impedance

Zbus = Vbase2 / Ssc = (33,000)2 / (2,000 × 106) = 0.5445 Ω

Step 3: Calculate total equivalent impedance

Ztotal = (Zgen × Zbus) / (Zgen + Zbus) = (1.742 × 0.5445) / (1.742 + 0.5445) = 0.412 Ω

Step 4: Calculate short-circuit current

Isc = VLL / (√3 × Ztotal) = 33,000 / (1.732 × 0.412) = 46,255 A = 46.26 kA

The total symmetrical short-circuit current at the 33 kV bus is approximately 46.26 kA.

Additional Technical Considerations

  • Asymmetrical Short-Circuit Current: The initial short-circuit current includes DC offset and can be up to 2.5 times the symmetrical RMS value. IEEE Std 141 provides methods to estimate this.
  • Effect of X/R Ratio: The ratio of reactance to resistance affects the DC offset and peak current magnitude, influencing protective device settings.
  • Motor Contribution: Motors connected to the system contribute additional short-circuit current during faults, typically accounted for by correction factors.
  • Voltage Correction Factors: IEC 60909 recommends voltage factors to consider operating voltage variations, ensuring conservative fault current estimates.
  • Transformer Connection Types: Delta or wye connections affect zero-sequence impedance and fault current paths, important for single line-to-ground fault calculations.

References and Further Reading

Understanding and accurately calculating short-circuit currents using the Infinite Bus Method is essential for power system protection and equipment specification. This article provides a comprehensive technical foundation aligned with IEEE and IEC standards, enabling engineers to perform reliable fault current analyses.