High Interrupting Capacity (AIC) Breaker Calculator – NEC

The design of electrical distribution systems must ensure efficiency, reliability, and absolute safety under fault conditions. The National Electrical Code defines requirements for minimum AIC breaker ratings to safely interrupt potential catastrophic failures.

 

High Interrupting Capacity (AIC) Breaker Calculator — NEC

 

Calculate the minimum AIC (kA) required and get suggested commercial breaker interrupting ratings. For design and NEC compliance confirm with local authority having jurisdiction (AHJ).

 
                                                         
    
             
    
   
      What does AIC (kA) mean?      
AIC (Ampere Interrupting Capacity) is the maximum fault current a breaker can safely interrupt, normally expressed in kA (kiloamperes) RMS symmetrical at rated voltage.
   
   
      What input should I provide?      
Provide the symmetrical RMS fault current in Amps at the point where the breaker will be installed. If you have peak or asymmetrical values, convert them first to symmetrical RMS per engineering practice.
   
   
      Formulas used      
        Required AIC (kA) = (Available Fault Current in A) / 1000.
        Recommended Rating = smallest commercial rating ≥ (Required AIC × (1 + margin)).
        Margin (%) can be set explicitly for additional safety (e.g., 20%).      
   
   
      Disclaimer      
This tool provides estimates. Always verify with manufacturer catalogs, upstream protective device coordination studies, and your Authority Having Jurisdiction (AHJ) before final selection.
   
 

What is High Interrupting Capacity (AIC)?

The AIC rating (sometimes called Interrupting Rating (IR) or Short-Circuit Current Rating (SCCR) for certain equipment) represents the maximum fault current a breaker can interrupt safely without failing.
It is expressed in amperes symmetrical RMS (A) or kiloamperes (kA) at a specified system voltage.

For example:

  • A breaker rated 10 kA @ 240 V can safely interrupt 10,000 amps of fault current at 240 volts AC.
  • If the available fault current exceeds this value, the breaker can explode or fail catastrophically, creating fire and arc-flash hazards.

NEC Requirements for AIC Rating

According to NEC Article 110.9 (Interrupting Rating):

Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the current that is available at the line terminals of the equipment.

This means:

  • The breaker’s AIC rating must be equal to or greater than the available short-circuit current (Isc) at the point of installation.
  • If a breaker with insufficient AIC is used, it violates NEC and poses a severe safety hazard.

Typical Commercial AIC Ratings of Breakers

Circuit breakers are manufactured with standardized interrupting ratings based on UL 489 and ANSI C37.13.
Below is an extended reference table showing common AIC values available in the U.S. market.

Table 1 – Common Breaker AIC Ratings by Voltage Class

Breaker TypeTypical Voltage ClassStandard AIC Ratings (kA RMS Sym)Notes
Miniature Circuit Breaker (MCB)120/240 V AC5, 10, 22 kAResidential, light commercial
Molded Case Circuit Breaker (MCCB)240 V AC10, 22, 25, 42, 65 kACommercial distribution panels
MCCB480 V AC14, 18, 25, 35, 42, 65, 100 kAIndustrial switchboards
MCCB600 V AC14, 18, 25, 35, 42, 65, 85, 100 kAHigher-voltage distribution
Low-Voltage Power Circuit Breaker480–600 V AC65, 85, 100, 150 kAUtility-grade protection
Medium Voltage Breaker2.4–15 kV25, 31.5, 40, 50, 63 kAANSI C37.06, utility systems
DC Rated Breakers125–600 V DC5, 10, 22, 50 kAData centers, solar, battery

These are catalog ratings, and the selected AIC must always exceed the calculated available fault current.

Fundamental Formulas for High Interrupting Capacity (AIC)

The AIC rating calculation is essentially a short-circuit current analysis at the point where the breaker is installed.

Formula 1 – Available Fault Current (Isc)

Where:

  • Isc = Available short-circuit current (A RMS symmetrical)
  • E = System line-to-line voltage (V)
  • Ztotal = Total system impedance from source to fault (Ω)

Notes:

  • Ztotal includes transformer impedance, conductor impedance, and source impedance.
  • For three-phase systems:

Formula 2 – Short-Circuit Current at Transformer Secondary

Where:

  • FLA = Full Load Amps of transformer secondary
  • %Z = Transformer impedance in %

This is one of the most commonly used quick methods in NEC-based fault current studies.

Formula 3 – Full Load Current of Transformer

Where:

  • kVA = Transformer rating in kilovolt-amperes
  • VLL = Line-to-line secondary voltage

Formula 4 – Available Fault Current at Service Entrance

Where:

  • Isc-transformer = Short-circuit current at transformer secondary
  • Xcable = Factor considering conductor impedance (length, size, material, temperature)

Formula 5 – Required Breaker AIC Rating

Where:

  • AICrequired = Minimum breaker interrupting rating (A RMS symmetrical)
  • Isc-available = Maximum calculated available fault current

Detailed Variable Explanation

To ensure clarity, below is a breakdown of each critical parameter:

VariableDescriptionCommon Range / Values
ESystem line-to-line voltage120 V, 208 V, 240 V, 277 V, 480 V, 600 V
ZtotalEquivalent impedance from source to faultDepends on transformer %Z, cable length, utility
%ZTransformer impedance percentage2% – 10% typical
kVATransformer capacity45, 75, 112.5, 150, 225, 300, 500, 750, 1000 kVA
FLATransformer full load ampsVaries with kVA and secondary voltage
XcableCable impedance correction factor0.7 – 0.95 typical
IscAvailable fault currentFrom 1,000 A to >100,000 A
AICrequiredBreaker minimum interrupting ratingMust be ≥ Isc

Extended Table of Typical Fault Current Values

The following table shows approximate available fault currents for common transformer sizes and secondary voltages, assuming 5% impedance and negligible cable length.
This serves as a reference starting point for engineers.

Table 2 – Fault Current Reference (3-Phase, 5% Z Transformers)

Transformer Size (kVA)Voltage (V LL)Full Load Amps (FLA)Fault Current (Isc) (A)Typical AIC Required (kA)
45 kVA208 V125 A2,500 A10 kA
75 kVA480 V90 A1,800 A10 kA
112.5 kVA480 V135 A2,700 A10 kA
150 kVA208 V416 A8,300 A10 kA
225 kVA480 V271 A5,400 A10 kA
300 kVA480 V361 A7,200 A10–22 kA
500 kVA480 V601 A12,000 A22–35 kA
750 kVA480 V902 A18,000 A25–42 kA
1000 kVA480 V1202 A24,000 A35–65 kA
2000 kVA480 V2405 A48,000 A65–100 kA

Real-World Case Study 1 – Commercial Building Service Entrance

Imagine a medium-sized commercial building with a 480 V three-phase service, supplied by a 750 kVA transformer provided by the utility. The transformer impedance is typical at 5%, and the service entrance main breaker is rated at 1,200 A.

An electrical engineer performs a fault current study to determine the available short-circuit current at the service disconnect. Based on utility data and transformer size, the study indicates an available fault current close to 18,000 amperes.

Now, the main breaker must be selected to withstand this fault current. If a 10 kA breaker were used, it would fail catastrophically under a fault condition. Instead, the engineer specifies a breaker with a 25 kA interrupting rating at 480 V. This ensures full compliance with NEC 110.9 and provides a safe margin above the calculated available fault current.

This example demonstrates how a seemingly standard breaker could be dangerously undersized if interrupting capacity is ignored. By correctly applying NEC principles, the building avoids severe safety risks and potential violations during inspection.

Real-World Case Study 2 – Industrial Motor Control Center (MCC)

Consider an industrial facility operating heavy machinery, with multiple 2,000 kVA transformers feeding a motor control center (MCC) at 480 V. Each transformer has 5% impedance and supplies multiple large induction motors.

The available short-circuit current at the MCC bus is calculated to be above 45,000 amperes. Breakers installed inside the MCC must therefore have AIC ratings of at least 65 kA at 480 V.

In practice, standard molded-case breakers often top out at 35 kA or 42 kA. To handle higher fault currents, engineers may specify:

  • High AIC molded-case breakers (65 kA or 100 kA ratings)
  • Current-limiting fuses in series with breakers to reduce available fault current to within the breaker’s capability
  • Power circuit breakers designed for utility-grade fault clearing

The solution in this case involved using 65 kA MCCBs, ensuring compliance with NEC and protecting workers from arc-flash hazards during fault conditions.

This example highlights how industrial facilities often require high-interrupting devices, and why coordination between utility data, transformer size, and breaker selection is critical.

Advanced Engineering Considerations in AIC Calculations

X/R Ratio and Asymmetrical Current

Short-circuit currents are not purely symmetrical. The X/R ratio (reactance-to-resistance ratio) of the system influences the asymmetrical component of fault current, which can significantly increase the first-cycle peak current.
Although breaker ratings are expressed in symmetrical RMS amperes, manufacturers test breakers with standard X/R ratios to ensure they can handle the additional stresses of asymmetrical fault currents.

Time-Current Coordination

When selecting breakers, engineers must also consider selective coordination with upstream and downstream devices. The breaker must not only have the correct AIC rating, but it must also trip selectively without unnecessarily shutting down other circuits. This is crucial in hospitals, data centers, and critical infrastructure.

Current-Limiting Devices

When available fault currents exceed the standard breaker ratings, current-limiting fuses or breakers are used to reduce the let-through energy. These devices clear the fault so quickly that the downstream breaker never experiences the full fault magnitude. This strategy allows the use of lower-AIC breakers in certain applications, provided the overall protective scheme is compliant with NEC.

Arc-Flash and Worker Safety

Beyond NEC compliance, high fault currents present a significant arc-flash hazard. A properly rated breaker not only prevents catastrophic equipment failure but also reduces the incident energy exposure to workers. Standards such as NFPA 70E provide guidelines for arc-flash calculations, PPE requirements, and safe work practices.

Common Mistakes in AIC Selection

  1. Relying only on catalog data without performing a short-circuit study.
  2. Assuming a 10 kA breaker is always adequate in commercial settings, which is often false.
  3. Ignoring transformer impedance values, leading to underestimation of available fault current.
  4. Not considering motor contribution, which can add thousands of amps during a fault.
  5. Failing to update breaker ratings after utility system upgrades that increase fault current.

Best Practices for NEC-Compliant Breaker Selection

  • Always request fault current data from the utility provider before design.
  • Perform a complete short-circuit and coordination study using software tools such as ETAP, SKM PowerTools, or EasyPower.
  • Select breakers with interrupting ratings equal or greater than the calculated available fault current.
  • Use current-limiting fuses where extremely high fault currents exist.
  • Regularly update studies and breaker ratings when system loads or utility services change.
  • Document AIC calculations clearly for compliance with NEC Article 110.9 and 110.10.

Extended Table – NEC Typical Breaker Applications by AIC Rating

ApplicationCommon VoltageTypical Available Fault CurrentRecommended Breaker AIC
Residential home service120/240 V< 10,000 A10 kA
Small retail shop120/240 V10,000 – 22,000 A22 kA
Medium commercial building480 V15,000 – 25,000 A25 kA
Large commercial facility480 V25,000 – 42,000 A35–42 kA
Industrial MCC480 V40,000 – 65,000 A65 kA
Utility-scale facility480–600 V65,000 – 100,000 A100 kA
Medium voltage switchgear4.16–15 kV25,000 – 63,000 A40–63 kA

This table is an excellent quick reference for engineers during preliminary design. Final breaker ratings must always be based on a detailed short-circuit study.