Fuse and Breaker Sizing Calculator – NEC

Accurate fuse and breaker sizing is critical for electrical safety and equipment protection. Understanding NEC guidelines ensures compliance and reliability.

This article explores the NEC-based fuse and breaker sizing calculations, providing formulas, tables, and real-world examples. Learn to size protective devices precisely.

Artificial Intelligence (AI) Calculator for “Fuse and Breaker Sizing Calculator – NEC”

Download TXT
  • Calculate breaker size for a 30A continuous load at 240V single-phase.
  • Determine fuse rating for a 15kW motor operating at 480V three-phase.
  • Find appropriate breaker size for a 100A feeder with 75°C conductors.
  • Calculate fuse size for a 60A load with 125% continuous current adjustment.

Comprehensive Tables for Fuse and Breaker Sizing According to NEC

Table 1: Common Circuit Breaker Sizes and Corresponding Wire Ampacities (NEC 310.15(B)(16))

Breaker Size (Amps)Conductor Size (AWG or kcmil)Conductor MaterialInsulation Temperature RatingAllowable Ampacity (Amps)
1514 AWGCopper60°C15
2012 AWGCopper60°C20
3010 AWGCopper75°C35
408 AWGCopper75°C50
506 AWGCopper75°C65
604 AWGCopper75°C85
1003 AWGCopper75°C100
1251 AWGCopper75°C130
1501/0 AWGCopper75°C150
2002/0 AWGCopper75°C175

Table 2: Typical Fuse Ratings for Motor Protection (NEC Article 430)

Motor Full Load Current (FLC) (Amps)Maximum Fuse Size (Amps)Minimum Fuse Size (Amps)Fuse Type
10175%125%Time-Delay
20175%125%Time-Delay
30175%125%Time-Delay
40175%125%Time-Delay
50175%125%Time-Delay
60175%125%Time-Delay
75175%125%Time-Delay
100175%125%Time-Delay

Table 3: Standard Breaker Sizes for Residential and Commercial Applications

Breaker Size (Amps)Typical ApplicationVoltage RatingInterrupting Rating (kAIC)
15Lighting Circuits120/240V10
20Small Appliance Circuits120/240V10
30HVAC Equipment120/240V10
40Water Heaters120/240V10
50Electric Ranges240V22
60Large HVAC Units240V22
100Subpanel Feeders240V22
150Large Motors480V42
200Main Service480V42

Essential Formulas for Fuse and Breaker Sizing According to NEC

Fuse and breaker sizing must comply with NEC requirements to ensure safety and equipment protection. The following formulas are fundamental.

1. Continuous Load Breaker Sizing

NEC 210.20(A) and 215.3 require that the breaker rating for continuous loads be at least 125% of the continuous load current.

Breaker Size (Amps) ≥ 1.25 × Continuous Load Current (Amps)
  • Breaker Size: The minimum circuit breaker rating in amperes.
  • Continuous Load Current: The load current expected to run for 3 hours or more continuously.

2. Non-Continuous Load Breaker Sizing

For non-continuous loads, the breaker size must be at least equal to the load current without the 125% multiplier.

Breaker Size (Amps) ≥ Load Current (Amps)

3. Motor Branch-Circuit Fuse Sizing (NEC 430.52)

Fuses protecting motors must be sized between 125% and 175% of the motor full-load current (FLC), depending on fuse type.

Fuse Size (Amps) = FLC × K
  • FLC: Motor full-load current from the motor nameplate or NEC Table 430.250.
  • K: Multiplier factor, typically 1.25 (minimum) to 1.75 (maximum) depending on fuse type and application.

4. Feeder Breaker Sizing (NEC 215.3)

Feeder breakers must be sized to handle the calculated load current plus any continuous load adjustment.

Breaker Size (Amps) ≥ 1.25 × Continuous Load + Non-Continuous Load
  • Continuous Load: Load expected to run for 3 hours or more.
  • Non-Continuous Load: Load expected to run less than 3 hours.

5. Conductor Ampacity Check

Conductor ampacity must be equal to or greater than the breaker size to prevent overheating and ensure safety.

Conductor Ampacity ≥ Breaker Size
  • Use NEC Table 310.15(B)(16) for ampacity values based on conductor size, insulation, and temperature rating.

Detailed Real-World Examples of Fuse and Breaker Sizing Using NEC Guidelines

Example 1: Sizing a Breaker for a Continuous Load Circuit

A commercial lighting circuit has a continuous load of 24 amps at 120 volts. Determine the minimum breaker size and conductor size.

  • Step 1: Calculate the minimum breaker size using the 125% rule.
Breaker Size ≥ 1.25 × 24A = 30A
  • Step 2: Select a standard breaker size equal to or greater than 30A. The next standard size is 30A.
  • Step 3: Choose conductor size based on NEC Table 310.15(B)(16). For 30A breaker, 10 AWG copper conductor with 60°C insulation is acceptable (ampacity 30A).

Result: Use a 30A breaker with 10 AWG copper conductors rated at 60°C or higher.

Example 2: Sizing a Fuse for a 15 kW Motor at 480V Three-Phase

A 15 kW, 480V, three-phase motor requires fuse protection. The motor full-load current (FLC) is calculated, and fuse size determined.

  • Step 1: Calculate motor full-load current using the formula:
FLC = (Power × 1000) / (√3 × Voltage × Power Factor × Efficiency)
  • Assuming Power Factor = 0.85 and Efficiency = 0.9 (typical values)
FLC = (15,000) / (1.732 × 480 × 0.85 × 0.9) ≈ 20.0 Amps
  • Step 2: Determine fuse size using NEC 430.52 (125% to 175% of FLC).
Minimum Fuse Size = 1.25 × 20A = 25A
Maximum Fuse Size = 1.75 × 20A = 35A
  • Step 3: Select a standard fuse size between 25A and 35A, typically 30A time-delay fuse.

Result: Use a 30A time-delay fuse to protect the 15 kW motor at 480V three-phase.

Additional Technical Considerations for Fuse and Breaker Sizing

  • Temperature Correction Factors: NEC requires adjusting conductor ampacity based on ambient temperature and conductor bundling (NEC 310.15(B)(2)(a)).
  • Voltage Rating: Ensure fuse and breaker voltage ratings match or exceed system voltage.
  • Interrupting Rating: Select devices with interrupting ratings equal to or greater than the available fault current at the installation point.
  • Selective Coordination: For critical systems, fuse and breaker sizing must consider coordination to minimize outage impact.
  • NEC Article 240: Provides detailed rules for overcurrent protection device selection and sizing.

Proper fuse and breaker sizing is a balance of safety, equipment protection, and code compliance. Using NEC guidelines ensures reliable electrical system performance.