Calculation of Short-Circuit Current in Transformers

Short-circuit current is essential in transformer design, influenced by rating, impedance, voltage, and configuration.
This table presents typical short-circuit currents for common transformer sizes, assuming a worst-case three-phase fault.

Short-Circuit Current in Transformer

Table 1: Common Transformer Short-Circuit Currents (Three-Phase Fault)

Transformer Rating (kVA)Primary Voltage (kV)Secondary Voltage (V)%Z (Impedance)Fault Level (kA)Short-Circuit MVA
10013.80.485.75%2.081.73
25013.80.485.75%5.214.33
50013.80.485.75%10.428.66
75013.80.485.75%15.6313.00
100013.80.485.75%20.8317.32
150013.80.485.75%31.2525.98
200013.80.485.75%41.6634.64
250013.80.485.75%52.0843.30

Note: These values assume no additional source impedance and no contribution from downstream motors. Always validate using system-specific data.

Key Formulas for Transformer Short-Circuit Current Calculation

Transformer short-circuit current calculation revolves around fundamental electrical formulas and per-unit systems. The primary formula is:

1. Short-Circuit Current at Transformer Secondary (Three-Phase):

Where:

2. Full Load Current Calculation:

Where:

  • S= Transformer apparent power (VA)
  • V= Line-to-line voltage (V)

3. Short-Circuit MVA Calculation:

4. Available Fault Current at Secondary Terminals:

5. Fault Current from Short-Circuit MVA:

Explanation of Each Variable and Typical Ranges

Real-World Application Examples

Example 1: Short-Circuit Current of a 500 kVA Transformer

Transformer Specifications:

  • Power Rating = 500 kVA
  • Voltage = 480 V (Secondary)
  • Impedance = 5.75%

Step 1: Calculate Full Load Current

Step 2: Calculate Short-Circuit Current

Result:

  • Short-Circuit Current at the secondary terminals = 10.45 kA

This current is used to size protective devices (breakers, fuses) and to determine arc flash levels.

Example 2: Large 2500 kVA Transformer Feeding a Switchgear

Transformer Specifications:

  • Power = 2500 kVA
  • Voltage = 480 V
  • Impedance = 6%

Step 1: Full Load Current

Step 2: Short-Circuit Current

Result:

  • The maximum short-circuit current could reach over 50 kA, which mandates high interrupting capacity breakers (e.g., 65kA-rated MCCBs).

Normative Reference and Practical Considerations

Normative Standards:

  • IEEE C37.010 – Guide for the Application of Faulted Current Calculations
  • IEEE 141 (Red Book) – Electric Power Distribution for Industrial Plants
  • IEC 60909 – Short-circuit currents in three-phase AC systems
  • NFPA 70 (NEC) – National Electrical Code, especially Article 450 and 240

Tip: Use IEEE Xplore or IEC Webstore to access standards.

Additional Considerations in Real Systems

  • Source Contribution: Utility or generator impedance reduces fault current.
  • X/R Ratio: Affects DC offset and breaker interrupting rating.
  • Transformer Winding Connection: Delta vs Wye affects zero-sequence impedance.
  • Motor Contribution: Motors downstream can significantly increase fault level.
  • Cable Impedance: Impacts fault level at distant points.

Typical Fault Current Multipliers by Transformer Size and Impedance

Transformer Size (kVA)Impedance %Fault Current Multiplier (xFLA)
100616.7
5005.7517.4
10005.7517.4
2500616.7

Advanced Case Study – Including Source and Cable Impedance

In practice, the short-circuit current at the load terminals of a transformer is affected by more than just the transformer impedance. It includes:

  1. Transformer impedance
  2. Source (utility or generator) impedance
  3. Cable impedance between transformer and load

Let’s demonstrate this with a real-world case.

Example 3: 1000 kVA Transformer with Utility and Cable Contribution

Specifications:

  • Transformer: 1000 kVA, 480 V, 5.75% impedance
  • Utility fault level: 500 MVA @ 13.8 kV
  • Cable: 20 m, 500 MCM copper, 3 conductors per phase
  • Load voltage: 480 V

Step 1: Transformer Full Load Current

Step 2: Transformer Impedance in Ohms

Step 3: Source Impedance (Utility)

First, convert utility fault level into impedance at the primary side:

Now reflect this to the secondary side (using turns ratio squared):

Step 4: Cable Impedance (per phase)

For 3×500 MCM copper over 20 m, using standard impedance:

Step 5: Total Impedance

Step 6: Calculate Short-Circuit Current

Result:
The available short-circuit current at the load terminals is approximately 2.5 kA, far less than the transformer-only fault current (~20.8 kA). This highlights the significant attenuation due to upstream and downstream impedance.

The Role of the X/R Ratio in Short-Circuit Current Calculations

The X/R ratio (reactance-to-resistance) plays a critical role in short-circuit analysis:

  • Affects the asymmetrical fault current
  • Influences breaker interrupting rating
  • High X/R ratios lead to higher peak fault currents

Asymmetrical Current Calculation:

Where:

Short-Circuit Current in Delta-Wye Transformers

Delta-Wye transformers isolate zero-sequence current, so single-line-to-ground faults must consider:

  • Zero-sequence impedance
  • Source grounding method
  • Wye secondary allows line-to-neutral fault return path

This requires:

  • Positive, negative, and zero sequence impedance modeling (per IEC 60909)
  • Fault type distinction (three-phase, SLG, L-L, L-L-G)

Important Real-World Design Applications

1. Breaker Sizing

  • Breakers must handle the maximum symmetrical and asymmetrical current
  • Example: If Isc = 50 kA, use breakers rated 65 kA or 100 kA interrupting

2. Arc Flash Analysis

  • Uses Isc in incident energy and PPE category calculation
  • Governed by IEEE 1584 and NFPA 70E

3. Equipment Withstand Ratings

  • Switchgear, panelboards, and busbars must have adequate withstand rating

Typical Breaker and Equipment Interrupting Ratings

Voltage ClassBreaker TypeCommon Interrupting Ratings (kA)
480 VMCCB10, 18, 25, 35, 65, 100
480 VPower Circuit Brkr25, 42, 65, 85, 100
13.8 kVVacuum Breaker16, 25, 31.5, 40

Always select devices with interrupting rating ≥ calculated Isc

Online Calculation Tools and Software

Free Online Calculators:

Professional Software:

  • ETAP – Advanced short-circuit studies, arc flash, coordination
  • SKM Power Tools
  • EasyPower
  • DigSILENT PowerFactory

Typical Transformer Impedance Values by Size and Type

Transformer Rating (kVA)Typical %Z (Dry Type)Typical %Z (Oil-Immersed)
752.5%3.0%
1503.5%4.0%
5005.75%5.75%
10005.75%5.75%
25006.0%6.0%
50006.5%6.5%

When Should You Perform Short-Circuit Calculations?

  • Before commissioning new transformers
  • During arc flash risk assessments
  • Before retrofitting switchgear or breakers
  • For utility interconnection studies
  • When adding generators, motors, or large loads

Best Practices for Engineers

  • Always consider system-wide impedance, not just transformer Z%
  • Use worst-case scenarios for design and protection
  • Validate all data with manufacturer datasheets
  • Update calculations with system modifications
  • Use professional software for coordination and selectivity

Useful References and External Resources