Calculation of Fuse and Circuit Breaker Sizing (NEC)

Proper sizing of fuses and circuit breakers ensures electrical safety, equipment protection, and NEC compliance. Incorrect sizing causes nuisance trips or unsafe conditions by failing to clear faults properly.

Fuse and Circuit Breaker Sizing (NEC)

Extensive Tables of Common Fuse and Circuit Breaker Sizing Values (NEC-Based)

The NEC provides guidelines to determine overcurrent protective device (OCPD) ratings based on conductor ampacity, load characteristics, and system type. Below are detailed tables of commonly used OCPD sizes, typical conductor ampacities, and associated load types.

Conductor AWG / SizeCopper Conductor Ampacity (NEC Table 310.16, 75°C)Typical OCPD Size (Amps)Common Application
14 AWG20 A15 A, 20 ALighting circuits, small branch circuits
12 AWG25 A20 A, 25 AGeneral branch circuits
10 AWG35 A30 A, 35 ABranch circuits for small motors or appliances
8 AWG50 A40 A, 50 ASmall motors, subpanels
6 AWG65 A60 A, 70 ALarger motors, feeders
4 AWG85 A70 A, 90 AFeeders, HVAC units
3 AWG100 A90 A, 100 AMain feeders
2 AWG115 A100 A, 125 AFeeders and branch circuits
1 AWG130 A125 A, 150 ALarger feeders, motor circuits
1/0 AWG150 A150 A, 175 ALarge motors, feeders
2/0 AWG175 A175 A, 200 AIndustrial feeders
3/0 AWG200 A200 A, 225 ALarger industrial feeders
4/0 AWG230 A225 A, 250 AIndustrial power circuits

Typical Fuse and Breaker Ratings for Motor Loads (NEC Article 430)

Motor HPFull Load Current (FLC) (Amps)Typical OCPD Rating (Amps)NEC Reference
1/2 HP4.810 – 15NEC 430.52
1 HP7.215 – 20NEC 430.52
3 HP17.025 – 35NEC 430.52
5 HP28.040 – 50NEC 430.52
7.5 HP34.045 – 60NEC 430.52
10 HP45.060 – 70NEC 430.52
15 HP65.090 – 100NEC 430.52
20 HP83.0100 – 125NEC 430.52
25 HP99.0125 – 150NEC 430.52

Common Standard Fuse Ratings (Ampere Classes)

Fuse TypeAmpere Rating (A)Common Applications
Class RK5 Fuse1, 2, 3, 4, 5, 6, 8, 10, 12, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200Industrial, motor protection, feeders
Class H Fuse1, 2, 3, 4, 5, 6, 8, 10, 12, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100Lighting, residential, small motors
Cartridge Fuse15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100General purpose, residential

Fundamental Formulas for Fuse and Circuit Breaker Sizing (NEC)

Sizing fuses and circuit breakers requires understanding the key formulas that relate load currents, conductor ampacity, and device ratings. Below are the main formulas and explanations for each variable used in sizing calculations.

1. Basic Load Current Calculation

Explanation: For three-phase loads, current is calculated by dividing power by the product of line voltage and power factor, normalized by For single-phase, remove

2. Maximum OCPD Rating for Continuous Loads

Per NEC 240.6(A) and 210.20(A):

Explanation: The OCPD must be sized to at least 125% of continuous load current to prevent nuisance tripping.

3. Conductor Ampacity Check

Explanation: The conductor must have an ampacity equal to or exceeding the OCPD rating to safely handle the expected load current.

4. Motor Overcurrent Device Sizing (NEC Article 430.52)

Explanation: Motor protection devices are sized as a percentage multiplier of the motor’s full load current.

5. Fuse Sizing for Transformer Primary Protection (NEC 450.3(B))

6. Breaker Interrupting Rating Check

Explanation: The device must be capable of interrupting the maximum available fault current at its installation point.

Detailed Explanation of Variables and Common Values

Real-World Application Examples

Example 1: Sizing a Circuit Breaker and Conductor for a 20 kW Three-Phase Motor Load at 480V

Given:

  • Motor Power P=20,000W (20 kW)
  • Voltage V=480V (three-phase)
  • Power Factor PF=0.9 (typical motor)
  • Continuous Load: Yes (motor runs for >3 hours)
  • Motor full load current from NEC Table 430.250: Approx. 28.8 A (for 20 kW, 480 V, 60 Hz)
  • Select breaker size and conductor.

Step 1: Calculate Full Load Current Iload

Using:

Step 2: Calculate Minimum OCPD Rating

Using motor multiplier from NEC 430.52, typically 125% for motor starters:

Choose the next standard breaker size: 40 A.

Step 3: Select Conductor Ampacity

Conductor ampacity must be ≥IOCPD=40A

From NEC 310.16:

  • 8 AWG copper conductor ampacity at 75°C = 50 A → adequate.
  • Choose 8 AWG copper conductor.

Step 4: Verify Interrupting Rating

Assuming fault current available at panel is 10kA:

  • Select breaker with interrupting rating ≥\geq≥ 10kA.

Example 2: Fuse Sizing for Transformer Primary Protection

Given:

  • Transformer rating: 75 kVA
  • Primary voltage: 480 V
  • Transformer primary current:

Step 1: Calculate Fuse Size

Using NEC 450.3(B) sizing factor of 125%:

Choose standard fuse size: 125 A Class RK5 fuse.

Step 2: Select Secondary Protection

  • Secondary rated at 208 V, 208 V side rated current:

Choose fuse or breaker accordingly on the secondary side.

Additional Considerations for Accurate Sizing

  • Ambient temperature correction: Per NEC 310.15(B)(2)(a), conductors must be derated for high temperatures.
  • Conductor bundling and conduit fill: Affects ampacity; apply adjustment factors.
  • Motor starting currents: Use time-delay fuses or breakers to allow inrush currents.
  • Selective coordination: Consider coordination between upstream and downstream devices to isolate faults.
  • Voltage drop: Ensure conductors are sized to limit voltage drop (max 3-5%).

References and Authoritative Resources