Cables for Transformers Calculator – NEC

Designing and sizing cables for transformers is essential, ensuring compliance, safety, reliability, and reduced voltage drop. This guide provides a detailed reference on transformer cable sizing calculations, including tables, real-world examples, and NEC rules.

Transformer Cable Sizing Calculator — NEC (kVA → Conductor)

Transformer Cable Sizing Calculator — NEC Guidance

Estimates conductor ampacity required for transformer secondary circuits (kVA → A) with common NEC practice.

Calculator shows required conductor ampacity and suggests nearest common copper sizes. Always confirm final conductor selection with NEC tables, local code, and engineer.
What formula does this use?
Single-phase: I = (kVA·1000) / V (or kW/(V·PF) if kW). Three-phase: I = (kVA·1000) / (√3·V). If kW is entered use PF. For continuous loads use multiplier (commonly 125%).
Does it replace NEC tables?
No — this is an engineering aid. Use NEC Chapter 3 & 9 tables for final conductor sizing, temperature correction, and adjustment factors.
Why 125%?
NEC practice commonly requires conductor ampacity not less than 125% of transformer full-load secondary current when used for continuous loads or as specified by NEC 450 series. Confirm with latest NEC and local amendments.

Why Transformer Cable Sizing Matters

Transformer cables connect primary and secondary windings to distribution systems, switchgear, and protective devices. Selecting the wrong cable size can lead to:

  • Excessive heating of conductors.
  • Failure to comply with NEC ampacity tables.
  • Increased electrical losses and reduced efficiency.
  • Higher risk of insulation breakdown.
  • Non-compliance with short-circuit withstand capability.

Thus, engineers must carefully apply NEC Article 450 (Transformers), Article 240 (Overcurrent Protection), and Article 310 (Conductors) to determine the correct cable size.

Common Cable Ampacity Values (NEC-Based Reference)

The following table summarizes commonly used copper conductor sizes (75°C insulation, THWN/THHN, in conduit, based on NEC Table 310.16). These values are the foundation for transformer cable sizing calculations.

Conductor Size (AWG/kcmil)Ampacity @ 75°C (A)Typical Application Voltage (V)Notes
14 AWG20 A120 V branchRarely used for transformers
12 AWG25 A120/240 VLight control circuits
10 AWG35 A240 VSmall control/auxiliary
8 AWG50 A240/480 VSmall dry-type transformer
6 AWG65 A240/480 VSecondary side ≤ 15 kVA
4 AWG85 A240/480 VSecondary side 25–30 kVA
3 AWG100 A480 V30–45 kVA transformers
2 AWG115 A480 V45 kVA secondary
1 AWG130 A480 V45–75 kVA
1/0 AWG150 A480 VCommon for 75 kVA
2/0 AWG175 A480 V100 kVA secondary
3/0 AWG200 A480 V112.5 kVA
4/0 AWG230 A480 V150 kVA
250 kcmil255 A480–600 V225 kVA
300 kcmil285 A480–600 V250 kVA
350 kcmil310 A480–600 V300 kVA
400 kcmil335 A480–600 V350 kVA
500 kcmil380 A480–600 V500 kVA
600 kcmil420 A480–600 V600 kVA
750 kcmil475 A480–600 V750 kVA
1000 kcmil545 A480–600 V1000 kVA

These are baseline ampacities. Adjustments must be made for:

  • Ambient temperature correction factors.
  • Conductor bundling / derating (NEC 310.15).
  • Voltage drop requirements (recommended ≤3%).

Fundamental Formulas for Transformer Cable Sizing

Transformer cable sizing relies on a set of core equations. Let’s break them down step by step.

1. Transformer Full Load Current (FLC)

Common transformer FLC values:

  • 45 kVA, 480 V → 54 A
  • 75 kVA, 480 V → 90 A
  • 150 kVA, 480 V → 180 A

2. Minimum Primary Conductor Sizing (NEC 450.3(B))

  • NEC requires 125% of rated current for transformer primary protection and conductor sizing.

3. Minimum Secondary Conductor Sizing (NEC 240.21(C))

  • Secondary conductors must also be sized at 125% of FLC, unless specific tap rules apply.

4. Voltage Drop Calculation

Recommended limits:

  • ≤ 3% for feeders.
  • ≤ 5% overall system.

5. Short-Circuit Withstand Check

Expanded Tables: Transformer kVA vs Cable Size (NEC 75°C)

The following table provides direct cable recommendations for common transformer sizes (three-phase, 480 V secondary, copper THWN/THHN, 75°C, NEC-compliant, assuming ≤75 ft run and ≤3% voltage drop).

Transformer Size (kVA)Secondary FLC (A)Min Cable Size (AWG/kcmil)Typical Primary Protection (OCPD)
15 kVA18 A#10 AWG30 A
30 kVA36 A#8 AWG60 A
45 kVA54 A#6 AWG70 A
75 kVA90 A#3 AWG125 A
112.5 kVA135 A1/0 AWG175 A
150 kVA180 A3/0 AWG225 A
225 kVA270 A350 kcmil350 A
300 kVA361 A500 kcmil450 A
500 kVA601 AParallel 2×500 kcmil800 A
750 kVA902 AParallel 3×500 kcmil1200 A
1000 kVA1202 AParallel 4×500 kcmil1600 A

Real-World Application Examples

Case Study 1: 75 kVA Transformer, 480 V to 208Y/120 V

Step 3: Select Cable Size

  • From NEC Table 310.16 → 300 kcmil copper (285 A @ 75°C).

Step 4: Voltage Drop Check

  • Assume 75 ft run, 208 A load.
  • Voltage drop < 3% → acceptable.

Recommended cable: 300 kcmil Cu, THWN, with 300 A breaker.

Case Study 2: 225 kVA Transformer, 480 V Secondary

Step 3: Select Cable

  • From NEC Table 310.16 → 350 kcmil Cu (310 A) not enough.
  • Next size up → 400 kcmil (335 A) still slightly low.
  • Final → 500 kcmil (380 A) → compliant.

Step 4: OCPD Selection

  • Choose 350 A breaker per NEC 450.3(B).

Recommended cable: 500 kcmil Cu, THWN, with 350 A OCPD.

Temperature Correction Factors for Transformer Cables

Cable ampacity values published in the NEC assume an ambient temperature of 30°C (86°F). However, in real-world installations, ambient temperatures are often higher, especially in electrical rooms, rooftops, or industrial environments. Failure to apply correction factors can result in undersized conductors.

The following table shows typical temperature correction factors for copper conductors rated 75°C and 90°C insulation:

Ambient Temperature (°C)Factor (75°C Insulation)Factor (90°C Insulation)
21–251.081.05
26–301.001.00
31–350.940.96
36–400.880.91
41–450.820.87
46–500.750.82
51–550.670.76
56–600.580.71

For example, if a 500 kcmil conductor has a base ampacity of 380 A at 30°C, and the installation temperature is 45°C, then the effective ampacity is 380 × 0.82 = 311 A. This can drastically change the cable size selection for large transformers.

Conduit Fill and Derating Considerations

Another factor often overlooked is conduit fill. NEC Article 310 requires derating when more than three current-carrying conductors are installed in the same raceway or cable tray.

  • 4–6 conductors → 80% of rated ampacity.
  • 7–9 conductors → 70% of rated ampacity.
  • 10–20 conductors → 50% of rated ampacity.

In transformer applications, parallel runs are common for large kVA units. When running three sets of parallel conductors per phase, conduit sizing and derating rules must be applied rigorously. Engineers must evaluate whether to use multiple conduits with fewer conductors per conduit to minimize derating and improve cooling.

Copper vs. Aluminum Conductors for Transformers

One of the most frequent design decisions is whether to use copper or aluminum cables. Both materials are NEC-approved, but they differ significantly in performance and cost.

CharacteristicCopperAluminum
ConductivityHigher (better ampacity per area)Lower (requires larger size)
WeightHeavierLighter (easier to handle in large sizes)
CostMore expensive30–50% cheaper
TerminationsLess prone to creepRequires anti-oxidant compound
Mechanical StrengthStrongerWeaker (larger bend radius)
Common UseCritical feeders, short runsLong feeders, large kVA transformers

In many projects, engineers choose aluminum conductors for large secondary feeders of 500 kVA and above due to cost savings, while copper conductors are reserved for primary feeders or installations where space, reliability, or mechanical strength are critical.

Practical Design Considerations

When sizing transformer cables, engineers must evaluate several practical conditions beyond ampacity:

  1. Distance and Voltage Drop
    • Runs exceeding 100 feet often require upsizing conductors.
    • The NEC does not mandate voltage drop limits, but industry standards recommend ≤3% for feeders and ≤5% overall.
  2. Short-Circuit Withstand
    • Conductors must withstand fault currents for the duration of protective device clearing time.
    • Larger kVA transformers with low-impedance ratings can deliver extremely high fault currents.
  3. Neutral and Grounding Conductors
    • For delta-wye transformers, the secondary neutral may need to carry significant harmonic currents, especially in systems with nonlinear loads (computers, drives, LED lighting).
    • Grounds must comply with NEC Article 250.
  4. Parallel Conductor Runs
    • For currents above 400 A, parallel runs are common.
    • NEC requires that parallel conductors be the same length, size, material, and termination.
  5. Future Expansion
    • Designers often oversize cables to allow for future load growth, avoiding costly upgrades later.

NEC Articles Relevant to Transformer Cable Sizing

  • Article 240: Overcurrent Protection – establishes rules for protective devices sizing.
  • Article 250: Grounding and Bonding – defines grounding electrode conductors and bonding requirements.
  • Article 310: Conductors for General Wiring – primary source for ampacity tables.
  • Article 450: Transformers – includes protection and installation requirements.
  • Article 310.15(B)(3): Adjustment factors for more than three conductors in a raceway.
  • Article 310.16: Ampacity tables for copper and aluminum conductors.

An engineer must reference all these sections when finalizing transformer cable sizing.